PHOENIX CONTACT 2801041
PHOENIX CONTACTNot available

VAL-MS-T1/T2 335/12.5/1+0 - Lightning/surge arrester type 1/2

Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with common N and PE (2-conductor system: L1, PEN).
Product Code: 2801041
Partner cod.: 2801041
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN-S
TN-C
TT
Type: DIN rail module, two-section, divisible
Product type: Arrester combination
Product family: VALVETRAB MS
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 3 Nm (1.5mm² ... 16mm²)
4.5 Nm (25mm²...35mm²)
Stripping length: 16 mm
Conductor cross section flexible: 1.5 mm² ... 25 mm²
1.5 mm² ... 16 mm²
Conductor cross section rigid: 1.5 mm² ... 35 mm²
Conductor cross section AWG: 15 ... 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/94ddaf9126a00d4d8a824e39b1a3e71f/-S204x204-FJPG
Width: 17.6 mm
Height: 89.8 mm
Depth: 77.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-N
L-PEN
Direction of action: L-N / L-PEN
Nominal voltage UN: 240VAC (TN-C, TN-S)
240VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 335 VAC
Rated load current IL: 80 A
Residual current IPE: ≤ 800 µA
Standby power consumption PC: ≤ 270 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 50 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Total discharge current Itotal (8/20)µs: 12.5 kA
Total discharge current Itotal (10/350)µs: 12.5 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Residual voltage Ures: ≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3kA)
TOV behavior at UT: 415 VAC (5s / withstand mode)
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 80 A (gG - 16 mm²)
Max. backup fuse with branch wiring: 160 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 65 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01874.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00573.pdf

Manufacturer_declaration_01991.pdf

Package_slip_00530.pdf

Technical_drawing_38497.pdf