PHOENIX CONTACT 2801532
PHOENIX CONTACTNot available

VAL-MS-T1/T2 48/12.5/1+1V - Lightning/surge arrester type 1/2

Universal varistor-based plug-in lightning/surge arrester for 48 V DC applications with grounded return conductor (positive pole), without risk assessment for Lightning Protection Levels III and IV.
Product Code: 2801532
Partner cod.: 2801532
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN-S
Type: DIN rail module, two-section, divisible
Product type: Arrester combination
Product family: VALVETRAB MS
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 3 Nm (1.5mm² ... 16mm²)
4.5 Nm (25mm²...35mm²)
Stripping length: 16 mm
Conductor cross section flexible: 1.5 mm² ... 25 mm²
1.5 mm² ... 16 mm²
Conductor cross section rigid: 1.5 mm² ... 35 mm²
Conductor cross section AWG: 15 ... 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/c05e789c438036478801116ca3a906ef/-S204x204-FJPG
Width: 35.6 mm
Height: 89.8 mm
Depth: 77.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 2 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-N
N-PE
L-PE
(L+) - (L-)
(L+) - PE
(L-) - PE
Direction of action: L-L / L-PE
Nominal voltage UN: 60VAC ±10% (TN-S)
60 VDC ±10%
-48 VDC ±10% (RRH)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 75 VAC
100 VDC
Rated load current IL: 80 A
Residual current IPE: ≤ 0.6 mA
Standby power consumption PC: ≤ 90 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 30 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Total discharge current Itotal (8/20)µs: 50 kA
Total discharge current Itotal (10/350)µs: 12.5 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up (L-N): ≤ 0.4 kV
Voltage protection level Up (L-PE): ≤ 0.8 kV
Voltage protection level Up (N-PE): ≤ 0.4 kV
Voltage protection level Up (L+) - (L-): ≤ 0.4 kV
Voltage protection level Up (L+) - PE: ≤ 0.4 kV
Voltage protection level Up (L-) - PE: ≤ 0.8 kV
Residual voltage Ures: ≤ 0.4 kV (at In)
≤ 0.35 kV (at 10 kA)
≤ 0.3 kV (at 5 kA)
≤ 0.275 kV (at 4 kA)
≤ 0.25 kV (at 3kA)
TOV behavior at UT: 100 VAC (5s / withstand mode)
130 VDC (5s / withstand mode)
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 80 A (gG - 16 mm²)
Max. backup fuse with branch wiring: 160 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 65 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV (L+) - (L-): 100 VDC
Maximum continuous operating voltage MCOV (L+) - G: 100 VDC
Maximum continuous operating voltage MCOV (L-) - G: 100 VDC
Short-circuit current rating (SCCR): 5 kA
Voltage protection rating VPR (L+) - (L-): 400 V
Voltage protection rating VPR (L+) - G: 400 V
Voltage protection rating VPR (L-) -G: 600 V
Nominal discharge current In (L+) - (L-): 20 kA
Nominal discharge current In (L+) - G: 20 kA
Nominal discharge current In (L-) - G: 20 kA
Mode of protection: (L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage: 60 VDC
SPD Type: 1CA
UL connection data
Tightening torque: 30 lbf-in.
Conductor cross section AWG: 14 ... 2
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600