Industrial Automation
VAL-MS 75 VF ST - Type 2 surge protection plug
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General Note: The values specified for the L-L protective path are only valid in connection with VAL-MS/2+0-BE/FM/S2 |
Product properties | IEC test classification: II T2 EN type: T2 Type: DIN rail module, two-section, divisible Product type: Replacement plug Product family: VALVETRAB MS Number of positions: 1 Surge protection fault message: optical Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Nominal voltage UN: 5 VAC ... 48 VAC |
Connection data | Connection method: pluggable |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3e02d9b64ee0a341a2e312513f1ad825/-S204x204-FJPG Width: 17.5 mm Height: 52.4 mm Depth: 55.3 mm Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6 Material group: I Housing material: PA 6.6 |
Protective circuit | Mode of protection: L-PE L-L Direction of action: 1L-N/PE Nominal voltage UN: 5 VAC ... 48 VAC Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 75 VAC 100 VDC Residual current IPE: ⤠5 µA Standby power consumption PC: ⤠1 mVA Nominal discharge current In (8/20) µs: 10 kA Maximum discharge current Imax (8/20) µs: 20 kA Short-circuit current rating ISCCR: 10 kA Voltage protection level Up: ⤠1.4 kV Voltage protection level Up (L-L): ⤠1.8 kV Residual voltage Ures: ⤠0.45 kV (at In) ⤠0.35 kV (at 5 kA) ⤠0.3 kV (at 3kA) Residual voltage Ures (L-L): ⤠0.9 kV (at In) ⤠0.7 kV (at 5 kA) ⤠0.6 kV (at 3kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.4 kV Response time tA: ⤠100 ns Max. backup fuse with branch wiring: 63 A (gG) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g Vibration (operation): 5g |
Approvals | UL specifications Maximum continuous operating voltage MCOV (L-N): 75 VAC Maximum continuous operating voltage MCOV (L+) - (L-): 100 VDC Nominal discharge current In (L-N): 10 kA Nominal discharge current In (L+) - (L-): 10 kA Mode of protection: L-N (L+) - (L-) Nominal voltage: 48VAC 60 VDC Power distribution system: Single phase Nominal frequency: 50/60 Hz Measured limiting voltage MLV (L-N): 1760 V Measured limiting voltage MLV (L+) - (L-): 1760 V SPD Type: 4CA |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: on base element |
ECLASS | ECLASS-11.0: 27130890 ECLASS-13.0: 27171292 |
ETIM | ETIM 9.0: EC002496 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products