Industrial Automation
Product properties | Product type: Signal conditioner Product family: MACX Analog No. of channels: 1 Type: Signal conditioners with SIL functional safety Configuration: DIP switches |
Electrical properties | Alignment span: ± 4 % Alignment zero: ± 4 % No. of channels: 1 Electrical isolation between input and output: yes Limit frequency (3 dB): 10 kHz (Can be switched to 30 Hz) Maximum power dissipation for nominal condition: < 0.7 W (20mA) Protective circuit: Transient protection Step response (10-90%): 35 µs (10kHz) 11 ms (30Hz) Maximum temperature coefficient: 0.0075 %/K Maximum transmission error: ⤠0.1 % (Compared to the final value) Electrical isolation Test voltage: 2.5 kV AC (50Hz, 60s) Overvoltage category: II Pollution degree: 2 Electrical isolation Input/output/power supply IEC/EN61010-1 Standards/regulations: IEC/EN61010-1 Rated insulation voltage: 300 Vrms Insulation: Safe isolation Electrical isolation Input/output/power supply IEC/EN60079-7 Standards/regulations: IEC/EN60079-7 Rated insulation voltage: 250 V AC/DC Supply Nominal supply voltage range: 12 VDC ... 24 VDC -20%...+25% Supply voltage range: 9.6 VDC ... 30 VDC Power dissipation: 500 mW (at 24 V DC / 20 mA) Power consumption: ⤠700 mW |
Input data | Signal: Voltage/current Number of inputs: 1 Voltage input signal: 0 mV ... 50 mV 0 mV ... 60 mV 0 mV ... 75 mV 0 mV ... 100 mV 0 mV ... 120 mV 0 mV ... 150 mV 0 mV ... 200 mV 0 mV ... 300 mV 0 mV ... 500 mV 0 V ... 1 V 0 V ... 1.5 V 0 V ... 2 V 0 V ... 3 V 0 V ... 5 V 0 V ... 10 V (Configurable via DIP switches) 0 V ... 15 V 0 V ... 20 V 0 V ... 30 V 0 V ... 50 V 0 V ... 100 V -50 mV ... 50 mV -60 mV ... 60 mV -75 mV ... 75 mV -100 mV ... 100 mV -120 mV ... 120 mV -150 mV ... 150 mV -200 mV ... 200 mV -300 mV ... 300 mV -500 mV ... 500 mV -1 V ... 1 V -1.5 V ... 1.5 V -2 V ... 2 V -3 V ... 3 V -5 V ... 5 V -10 V ... 10 V -15 V ... 15 V -20 V ... 20 V -30 V ... 30 V -50 V ... 50 V -100 V ... 100 V 1 V ... 5 V 2 V ... 10 V Min. voltage input signal: ± 50 mV Max. voltage input signal: ± 100 V Current input signal: 0 mA ... 1 mA (Configurable via DIP switches) 0 mA ... 1.5 mA 0 mA ... 2 mA 0 mA ... 3 mA 0 mA ... 5 mA 0 mA ... 10 mA 0 mA ... 15 mA 0 mA ... 20 mA 0 mA ... 30 mA 0 mA ... 50 mA 0 mA ... 100 mA -1 mA ... 1 mA -1.5 mA ... 1.5 mA -2 mA ... 2 mA -3 mA ... 3 mA -5 mA ... 5 mA -10 mA ... 10 mA -15 mA ... 15 mA -20 mA ... 20 mA -30 mA ... 30 mA -50 mA ... 50 mA -100 mA ... 100 mA 1 mA ... 5 mA 2 mA ... 10 mA 4 mA ... 20 mA Minimum current input signal: ± 1 mA Max. current input signal: ± 100 mA Input resistance of voltage input: approx. 1 Mé (±1VDC... ±100VDC) Input resistance current input: approx. 10 é (±10mADC...±100mADC) |
Output data | Signal: Voltage/current Number of outputs: 1 Configurable/programmable: Yes, can be switched Voltage output signal: 0 V ... 10 V (Configurable via DIP switches) 0 V ... 5 V 2 V ... 10 V 1 V ... 5 V -10 V ... 10 V -5 V ... 5 V 0 V ... 2.5 V 0.5 V ... 2.5 V -2.5 V ... 2.5 V Output signal voltage inverse: 0 V ... 2.5 V 0 V ... 5 V 0 V ... 10 V Current output signal: 0 mA ... 5 mA 0 mA ... 10 mA 0 mA ... 20 mA (Configurable via DIP switches) 1 mA ... 5 mA 2 mA ... 10 mA 4 mA ... 20 mA -5 mA ... 5 mA -10 mA ... 10 mA -20 mA ... 20 mA Output signal current inverse: 0 mA ... 5 mA 0 mA ... 10 mA 0 mA ... 20 mA Load/output load voltage output: ⥠1 ké (10V) Load/output load current output: ⤠600 é (20 mA; active) passive: ⤠(UB-2 V) / Ioutmax Ripple: < 10 mVrms |
Connection data | Connection method: Screw connection Stripping length: 7 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 14 Tightening torque: 0.5 Nm ... 0.6 Nm Test socket Max. diameter: 2 mm |
Ex data | Ex installation (EPL): Gc Div.2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG Width: 12.5 mm Height: 112.5 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -20°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude range (⤠2000 m) Altitude: ⤠2000 m (The technical data refers to altitudes â¤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.) Ambient temperature (operation): -20°C ... 70°C Altitude range (⤠3000 m) Height range: > 2000 m ... 3000 m Ambient temperature (operation): -20°C ... 60°C Rated insulation voltage: 190 V Altitude range (⤠4000 m) Height range: > 3000 m ... 4000 m Ambient temperature (operation): -20°C ... 55°C Rated insulation voltage: 63 V Altitude range (⤠5000 m) Height range: > 4000 m ... 5000 m Ambient temperature (operation): -20°C ... 45°C Rated insulation voltage: 63 V |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 10 ATEX E 059 X UKCAEx(UKEX) Identification: ï II 3 G Ex nA IIC T4 Gc Certificate: PxCIF21UKEX2811284X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 10.0044X CCC/China-Ex Identification: Ex ec IIC T4 Gc Certificate: 2021122304114077 UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC Shipbuilding approval Certificate: DNV GL TAA000020C Safety Integrity Level (SIL, IEC 61508) Identification: 2 INMETRO Identification: Ex ec IIC T4 Gc Certificate: DNV 21.0063 X DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 1 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 1 % Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 1 % |
Standards and regulations | GBStandard Standards/regulations: GB/T3836.1 GB/T3836.3 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
ECLASS | ECLASS-11.0: 27210120 ECLASS-12.0: 27210120 ECLASS-13.0: 27210120 |
ETIM | ETIM 8.0: EC002653 |
UNSPSC | UNSPSC 21.0: 39121000 |