Industrial Automation
Notes | General Note: Usable in all low-voltage systems between L-N or L-PEN. Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
Product properties | IEC test classification: II T2 EN type: T2 IEC power supply system: TN TT IT Type: DIN rail module, two-section, divisible Product type: Surge arrester Product family: VALVETRAB MS Number of positions: 1 Surge protection fault message: optical Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) |
Connection data | Connection method: Screw connection Fork-type cable lug Screw thread: M5 Tightening torque: 3 Nm (1.5mm² ... 16mm²) 4.5 Nm (25mm²...35mm²) Stripping length: 16 mm Conductor cross section flexible: 1.5 mm² ... 25 mm² 1.5 mm² ... 16 mm² Conductor cross section rigid: 1.5 mm² ... 35 mm² Conductor cross section AWG: 15 ... 2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9b15394f5dd67f449a8598d0e082051f/-S204x204-FJPG Width: 17.6 mm Height: 89.8 mm Depth: 65.7 mm (incl. DIN rail 7.5mm) Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6/PBT Material group: I Housing material: PA 6.6 PBT |
Protective circuit | Mode of protection: L-N L-PE L-PEN Direction of action: 1L-N/PE Nominal voltage UN: 240/415VAC (TN) 240/415VAC (TT) 230VAC (IT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 350 VAC Rated load current IL: 80 A Residual current IPE: ⤠5 µA Standby power consumption PC: ⤠2 mVA Nominal discharge current In (8/20) µs: 10 kA Maximum discharge current Imax (8/20) µs: 20 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up: ⤠1.5 kV Residual voltage Ures: ⤠1.2 kV (at In) ⤠1.2 kV (at 10 kA) ⤠1.1 kV (at 5 kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.5 kV TOV behavior at UT: 415 VAC (5s / withstand mode) 440 VAC (120min / withstand mode) Response time tA: ⤠100 ns Max. backup fuse with V-type through wiring: 80 A (gG) Max. backup fuse with branch wiring: 125 A (gG) Additional technical data Impulse discharge current (10/350)µs, charge: 0.25 As Impulse discharge current (10/350)µs, specific energy: 62.5 J/é Impulse discharge current (10/350)µs, peak value limp: 500 A |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV (L-N): 350 VAC Nominal discharge current In (L-N): 10 kA Mode of protection: L-N Nominal voltage: 240VAC Power distribution system: Single phase Nominal frequency: 50/60 Hz Measured limiting voltage MLV (L-N): 2420 V SPD Type: 4CA UL connection data Tightening torque: 30 lbf-in. Conductor cross section AWG: 14 ... 2 |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 9.0: EC000941 |