Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2864095
PHOENIX CONTACTAvailable

MINI MCR-SL-R-UI - Resistance/potiposition transducer

MCR potiposition transducer for conversion of potentiometer positions into a standard analog signal, 0 Ω input... 100 Ω to 0 kΩ ... 100 kΩ
Product Code: 2864095
Partner cod.: 2864095
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Potiposition transducer
Product family: MINI Analog
No. of channels: 1
Configuration: DIP switches
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
System propertiesFunctionality
Configuration: DIP switches
Electrical propertiesNo. of channels: 1
Maximum power dissipation for nominal condition: 235.5 mW
Step response (0–99%): < 30 ms
Maximum temperature coefficient: < 0.02 %/K
Temperature coefficient, typical: < 0.02 %/K
Maximum transmission error: < 0.2 %
Electrical isolation Input/output/power supply
Rated insulation voltage: 30 VAC
50 VDC
Test voltage: 1.5 kV AC (50Hz, 60s)
Insulation: Basic insulation in accordance with IEC/EN61010
Supply
Nominal supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Typical current consumption: < 25 mA (at 24 V DC)
Power consumption: < 500 mW
Input dataSignal: Resistance
Number of inputs: 1
Resistance range: 100 Ω ... 100 kΩ
Reference voltage source: < 3.6 V
Output dataSignal: Voltage/current
Number of outputs: 1
Voltage output signal: 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal: 12.5 V
Non-load voltage:  12.5 V
Current output signal: 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal: 23 mA
Short-circuit current:  10 mA
Load/output load voltage output: > 10 kΩ
Load/output load current output: < 500 Ω (20mA)
Ripple: < 20 mVPP (500 Ω)
< 20 mVPP (10kΩ)
Behavior in the event of a sensor error: 0 % ... 105 % (configurable)
Connection dataConnection method: Screw connection
Stripping length: 12 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 26 ... 12
SignalingError indication: Red LED
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG
Width: 6.2 mm
Height: 93.1 mm
Depth: 101.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20°C ... 65°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
UL, USA/Canada
Identification: UL508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Shipbuilding approval
Certificate: DNV GL TAA000020N
DNV GL data
Temperature: B
Humidity: B
Vibration: B
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 5 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 5 %
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 5 %
MountingMounting type: DIN rail mounting
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210120
ECLASS-12.0: 27210120
ECLASS-13.0: 27210120
ETIMETIM 9.0: EC002653
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01943.pdf

Data_sheet_03571.pdf

Manual_00026.pdf

Manufacturer_declaration_00562.pdf

Manufacturer_declaration_02347.pdf

Manufacturer_declaration_15258.pdf

Package_slip_01662.pdf

Product_information_00015.pdf

Product_information_00033.pdf

Product_information_00456.pdf

Technical_drawing_38968.pdf