Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Repeater power supplies Product family: MINI Analog No. of channels: 1 Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | No. of channels: 1 Electrical isolation: 3-way isolation Electrical isolation between input and output: yes Limit frequency (3 dB): approx. 100 Hz Maximum power dissipation for nominal condition: 508 mW (24VDC) 208 mW (24VDC) Protective circuit: Transient protection Signal transmission behavior: In=Out Step response (10-90%): ï» 3.5 ms Maximum temperature coefficient: < 0.01 %/K Temperature coefficient, typical: < 0.002 %/K Maximum transmission error: ⤠0.2 % (of final value) Transmission error, typical: ⤠0.1 % (of final value) Electrical isolation Input/output/power supply Rated insulation voltage: 50 V AC/DC Test voltage: 1.5 kV AC (50Hz, 60s) Insulation: Basic insulation in accordance with IEC/EN61010 Supply Nominal supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Power consumption: < 900 mW (at 24 V DC and in repeater power supply operation) < 600 mW (at 24 V DC and in isolator operation) |
Input data | Signal: Current Description of the input: Sensor circuit Number of inputs: 1 Current input signal: 0 mA ... 20 mA (isolator operation) 4 mA ... 20 mA (repeater power supply and isolator operation) Max. current input signal: 28 mA Input resistance current input: approx. 50 é Transmitter supply voltage: UB - max. 4.5 V for load 0 mA ... 20 mA Transmitter supply voltage range: 14.7 VDC ... 25.5 VDC |
Output data | Signal: Current Number of outputs: 1 Non-load voltage: approx. 12.5 V Current output signal: 0 mA ... 20 mA (isolator operation) 4 mA ... 20 mA (repeater power supply and isolator operation) Max. current output signal: 28 mA Load/output load current output: ⤠500 é (I = 20 mA) Ripple: < 20 mVrms (at 500 é) |
Connection data | Connection method: Screw connection Stripping length: 12 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 26 ... 12 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG Width: 6.2 mm Height: 93.1 mm Depth: 101.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant UL, USA/Canada Identification: UL508 Recognized Class I, Div. 2, Groups A, B, C, D T5 Shipbuilding approval Certificate: DNV GL TAA000020N DNV GL data Temperature: B Humidity: B Vibration: B EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 10 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 10 % Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Comments: Criterion B Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 10 % |
Standards and regulations | Electrical isolation: 3-way isolation |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715. Mounting position: any |
ECLASS | ECLASS-11.0: 27210120 ECLASS-12.0: 27210120 ECLASS-13.0: 27210120 |
ETIM | ETIM 9.0: EC002653 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products