TRIO-PS/3AC/24DC/10 - Power supply unit

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 3-phase, output: 24 V DC/10 A
Product Code: 2866459
Partner cod.: 2866459
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Input dataAC operation
Nominal input voltage range: 2x / 3x 400 VÂAC ... 500 VÂAC
Input voltage range: 3x 320 VÂAC ... 575 VÂAC
2x 360 VÂAC ... 575 VÂAC (for 2-phase operation)
Input voltage range AC: 3x 320 VÂAC ... 575 VÂAC
2x 360 VÂAC ... 575 VÂAC (for 2-phase operation)
Voltage type of supply voltage: AC
Inrush current: < 15 A
Inrush current integral (I2t): 0.2 A2s
AC frequency range: 45 Hz ... 65 Hz
Mains buffering time: > 20 ms (3x 400 V AC)
Current consumption: 3x 0.6 A (400ÂVÂAC)
3x 0.5 A (480ÂVÂAC)
Nominal power consumption: 456 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.59
Typical response time: < 1 s
Strike voltage of gas-filled surge arrester (input to PE): <
Input fuse: <
Permissible backup fuse: B6 B10 B16
Permissible DC backup fuse: <
Recommended breaker for input protection: < 6 A ... 16 A (Characteristics B, C, D, K)
Recommended fuse for input protection: <
Discharge current to PE: < 3.5 mA
Output dataEfficiency: 88.5 % (at 400 V AC and nominal values)
Output characteristic: U/I
Nominal output voltage: 24 VÂDC ±1Â%
Setting range of the output voltage (USet): 22.5 VÂDC ... 29.5 VÂDC (> 24 VÂDC, constant capacity restricted)
Nominal output current (IN): 10 A (UOUT = 24 V DC)
Derating: 55°C ... 70°C (2.5%/K)
Feedback voltage resistance: 35 VÂDC
Protection against overvoltage at the output (OVP): < 35 VÂDC
Max. capacitive load: unlimited
Active current limitation: approx. 15 A
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 10 mVPP
Output power: 240 W
Peak switching voltages nominal load: < 30 mVPP
Maximum no-load power dissipation: 7.5 W
Power loss nominal load max.: 34 W
Rise time: < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 9 mm
Screw thread: M2,5
Tightening torque, min: 0.4 Nm
Tightening torque max: 0.5 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 16
Conductor cross section AWG max.: 12
Stripping length: 9 mm
Screw thread: M2,5
Tightening torque, min: 0.4 Nm
Tightening torque max: 0.5 Nm
SignalingTypes of signaling: LED
Operating voltage display: Green LED
Signal output
Status display: "DC OK" LED green
Note on status display: UOUT > 21.5 V: LED lights up
Electrical propertiesInsulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VÂDC (routine test)
Insulation voltage input / PE: 2 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 1156000 h
Insulation characteristics
Protection class: I (with PE connection)
Overvoltage category: III
Degree of pollution: 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/688a44da5e666d4e8acd726a889bc6b0/-S204x204-FJPG
Width: 60 mm
Height: 130 mm
Depth: 152.5 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingAssembly instructions: alignable: horizontally 0Âmm, vertically 50Âmm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Steel sheet, zinc-plated
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsStandard âۉ€œ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÂ50178/VDEÂ0160 (PELV)
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: ENÂ60950-1/VDEÂ0805 (SELV)
Standard âۉ€œ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÂ50178
Standard âۉ€œ Safety extra-low voltage: ENÂ60950-1 (SELV)
ENÂ60204 (PELV)
Standard - Safe isolation: DINÂVDEÂ0100-410
ApprovalsUL approvals: UL/C-UL listed ULÂ508
UL/C-UL Recognized ULÂ60950-1
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: ENÂ61000-4-11
Emitted interference
Standards/regulations: ENÂ61000-6-3
Radio interference voltage in acc. with EN 55011: ENÂ55011 (ENÂ55022) ClassÂB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_01850.pdf

Data_sheet_03640.pdf

Manufacturer_declaration_02999.pdf

Manufacturer_declaration_04707.pdf

Manufacturer_declaration_05508.pdf

Manufacturer_declaration_15315.pdf

Package_slip_02458.pdf

Technical_drawing_39046.pdf

Various_00006.pdf