Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2866718
PHOENIX CONTACTNot available

QUINT-PS/1AC/12DC/15 - Power supply unit

Primary-switched power supply unit QUINT POWER, Pluggable screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input:1-phase, output: 12 VDC / 15 A
Product Code: 2866718
Partner cod.: 2866718
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataNominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 85 VAC ... 264 VAC
90 VDC ... 350 VDC (UL 508: ≤ 250 V DC)
Input voltage range AC: 85 VAC ... 264 VAC
Input voltage range DC: 90 VDC ... 350 VDC (UL 508: ≤ 250 V DC)
Electric strength, max.: 300 VAC
Voltage type of supply voltage: AC/DC
Inrush current: < 15 A (typical)
Inrush current integral (I2t): < 1.5 A2s
AC frequency range: 45 Hz ... 65 Hz
Frequency range DC: 0 Hz
Mains buffering time: > 65 ms (120VAC)
> 65 ms (230 V AC)
Current consumption: 1.9 A (120VAC)
0.9 A (230 V AC)
1.9 A (110VDC)
0.9 A (220 VDC)
Nominal power consumption: 210 VA
Protective circuit: Transient surge protection; Varistor
Typical response time: < 0.5 s
Input fuse: 6.3 A (slow-blow, internal)
Permissible backup fuse: B10 B16 AC:
Permissible DC backup fuse: DC: Connect a suitable fuse upstream
Recommended breaker for input protection: 10 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: > 89 % (for 230 V AC and nominal values)
Output characteristic: U/I
Nominal output voltage: 12 VDC ±1%
Setting range of the output voltage (USet): 5 VDC ... 18 VDC (> 12 VDC, constant capacity restricted)
Nominal output current (IN): 15 A (-25°C...60°C)
POWER BOOST (IBoost): 16 A (-25°C...40°C permanent)
Selective Fuse Breaking (ISFB): 60 A (12ms)
Magnetic circuit breaker tripping: B2 / B4 / B6 / C2 / C4
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: max. 25 VDC
Protection against overvoltage at the output (OVP): < 25 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 10 mVPP (with nominal values)
Short-circuit-proof: yes
Output power: 180 W
Maximum no-load power dissipation: 5 W
Power loss nominal load max.: 21 W
Rise time: < 0.5 ms
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 0.9 x UN: High signal
Switching voltage range: 5 VDC ... 12 VDC
Output voltage: 12 VDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Signal: DC OK floating
Output description: Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage: 30 VAC
24 VDC
Maximum inrush current: 0.5 A
1 A
Continuous load current: 1 A
Signal: POWER BOOST, active
Output description: IOUT < IN: High signal
Switching voltage range: 5 VDC ... 12 VDC
Output voltage: 12 VDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Connection dataInput
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 16
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 16
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 16
Conductor cross section AWG max.: 12
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Relay contact
Signal output: DC OK active
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
IOUT < IN: LED ON
Signal output: DC OK floating
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
Signal output: POWER BOOST, active
Status display: IOUT > IN: LED "BOOST" yellow
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VDC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 1000000 h (25°C)
> 570000 h (40°C)
> 250000 h (60°C)
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsWidth: 60 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 63 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: PN ≥50%, 5mm horizontally, 15mm next to active components, 50mm vertically
alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Steel sheet, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: 5000 m
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: EN50121-4
EN50121-3-2
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 61010-2-201(SELV)
Standard - Equipment safety: GS (tested safety)
Standard - Approval for medical use: IEC 60601-1, 2xMOOP
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178
Standard – Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Overvoltage category
EN 62477-1: III
ApprovalsCSA: CAN/CSA-C22.2 No.60950-1-07
CSA-C22.2 No.107.1-01
UL approvals: UL Listed UL508
UL/C-UL Recognized UL60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00192.pdf

Data_sheet_03655.pdf

Manufacturer_declaration_03094.pdf

Manufacturer_declaration_04722.pdf

Manufacturer_declaration_05497.pdf

Manufacturer_declaration_15334.pdf

Package_slip_02059.pdf

Product_information_00152.pdf

Technical_drawing_39065.pdf

Various_00006.pdf