PHOENIX CONTACT 2867979
PHOENIX CONTACT 2867979
PHOENIX CONTACTNot available

EMD-FL-3V-500 - Monitoring relay

Monitoring relay for monitoring 3-phase voltages of 350…650 V AC, undervoltage, window, phase sequence, phase failure, asymmetry, supply voltage can be selected via power module, 2 changeover contacts
Product Code: 2867979
Partner cod.: 2867979
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Product propertiesProduct type: Voltage monitoring relay
Operating mode: 100% operating factor
Mechanical service life: approx. 2x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Insulation characteristicsâۉ€¹
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 2
Electrical propertiesService life electrical: 2x 105 cycles at ohmic load, 1000 VA
Mains type: 3-phase
Rated insulation voltage: 600 V
Rated surge voltage: 6 kV
Supply
Supply voltage range: 230 VÂAC ... 500 VÂAC (see Power modules)
Nominal power consumption: 4.5 VA (1.5ÂW)
Input dataInput name: Measuring input
Measured value: AC sine (48 Hz ... 63 Hz)
Protection: ≤ 20 A
Nominal input voltage UN: 3 ~ 500 V
Maximum input voltage: 3 ~ 700 V
Input resistance of voltage input: 1 MΩ
Frequency range: 50 Hz ... 60 Hz
Maximum temperature coefficient: < 0.1 %/K
Setting range for response delay: 0.1 s ... 10 s
Min. setting range: -30 % ... 20 % (From UN)
Max. setting range: -20 % ... 30 % (From UN)
Min setting range of the voltage threshold value: 350 VÂAC ... 600 VÂAC
Max. setting range of the voltage threshold value: 400 VÂAC ... 650 VÂAC
Function: Undervoltage
Window
Asymmetry
Phase sequence
Phase failure
Basic accuracy: ± 5 % (of scale end value)
Setting accuracy: ≤ 5 % (of scale end value)
Repeat accuracy: ≤ 2 %
Asymmetry: 5Â% ... 25% / OFF
Recovery time: 500 ms
Output dataSwitching
Contact switching type: 2 floating changeover contacts
Maximum switching voltage: 250 VÂAC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.: 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse: 5 A (fast-blow)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Conductor cross section rigid: 0.5 mm² ... 2.5 mm²
Conductor cross section flexible: 0.25 mm² ... 2.5 mm²
Conductor cross section AWG: 20 ... 14
DimensionsWidth: 45 mm
Height: 90 mm
Depth: 113 mm
Material specificationsHousing insulation material: Polyamide PA, self-extinguishing
Environmental and real-life conditionsAmbient conditions
Degree of protection (Housing): IP40 (Housing)
Degree of protection (Connection terminal blocks): IP20 (Connection terminal blocks)
Ambient temperature (operation): -25°C ... 55°C
-25°C ... 40°C (corresponds to ULÂ508)
Ambient temperature (storage/transport): -25°C ... 70°C
Climatic class: 3K3 (in acc. with EN 60721)
Permissible humidity (operation): 15 % ... 85 %
ApprovalsCE
Certificate: CE-compliant
UL, USA/Canada
Identification: UL/C-UL Listed UL 508
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Noise immunity: EN 61000-6-2
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-3
Standards and regulationsStandards/regulations: ENÂ50178
MountingMounting type: DIN rail mounting
Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715
Mounting position: any
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03669.pdf

Manufacturer_declaration_01617.pdf

Manufacturer_declaration_04696.pdf

Package_slip_01001.pdf