Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/20a984302842e949b5ce7beb58df3766/-S204x204-FJPG Width: 48.8 mm Height: 136 mm Depth: 71.5 mm |
Interfaces | Inline local bus Number of interfaces: 2 Connection method: Inline data jumper Transmission speed: 2 Mbps Transmission physics: Copper |
System properties | Module ID code (dec.): 223 ID code (hex): DF Length code (hex): 03 Length code (dec): 03 Process data channel: 48 bit Input address area: 48 bit Output address area: 48 bit Register length: 32 bit Required parameter data: 15 Byte Required configuration data: 5 Byte |
Input data | Analog Description of the input: Input channels for strain gauge Number of inputs: 2 Connection technology: 6 or 4-wire, twisted pair shielded cable Bridge difference Ud: Measuring range specified by selecting the characteristic and the bridge voltage Bridge voltage U0: 3.3 V 5 V Measured value representation: 15 bit + sign bit Characteristics: ±1mV/V, ±2mV/V, ±3mV/V, ±4mV/V +1mV/V, +2mV/V, +3mV/V, +4mV/V |
Output data | Analog Output description: Voltage output Number of outputs: 2 Impedance: > 58.3 é (typical; permissible total resistance of the strain gauge) Output voltage: 5 V 3.3 V Output current: typ. 55 mA (with UV = 3.3 V) typ. 85 mA (with UV = 5 V) |
Product properties | Type: modular Product type: I/O component Product family: Inline Operating mode: Process data operation with 3 words, PCP with 1 word Diagnostics messages: Failure of the power supply at UANA Error message in the process data Failure of or insufficient communications power UL I/O error message sent to the bus coupler I/O error Error message in the process data |
Electrical properties | Potentials Power consumption: typ. 0.94 W (Device in nominal operation) Potentials: Communications power (U Supply voltage: 7.5 VDC (via voltage jumper) Current draw: max. 110 mA typ. 100 mA Potentials: Supply of analog modules (U Supply voltage: 24 VDC (via voltage jumper) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: typ. 32 mA (with maximum load of 58.3 é when UV = 5 V) typ. 8 mA (without strain gauge) Electrical isolation/isolation of the voltage ranges Test voltage: Logic/analog I/O (digital isolator): 500 VAC, 50 Hz, 1 min. Test voltage: Functional ground/analog I/O (isolating distance): 500 VAC, 50 Hz, 1 min. Test voltage: Logic/functional ground (isolating distance): 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |
ETIM | ETIM 9.0: EC001596 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products