Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2882213
PHOENIX CONTACTNot available

MNT-1 D/WH - Type 3 surge protection device

Attachment connector with surge protection for mains sockets, mains control lamp, optical power and error display. For country-specific use in: D, A, I, NL, S, N, FIN, E, P. Color: White
Product Code: 2882213
Partner cod.: 2882213
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC power supply system: TN
TT
Type: Attachment plug
Product type: Device protection
Product family: MAINTRAB
Number of positions: 2
For country-specific use in: D, A, NL, E, S, FIN, TR
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
IEC test classification: III
T3
EN type: T3
Number of ports: One
Connection dataConnection method: Grounding plug/socket
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d00ae81c2fb1c54c8bd11dab4ac9ceb7/-S204x204-FJPG
Width: 56 mm
Height: 76 mm
Depth: 78 mm
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 400
600
Insulating material: PA 6
Housing material: PA 6
Protective circuitMode of protection: L-N
L-PE
N-PE
Direction of action: L(N)-PE
Nominal voltage UN: 230/400VAC(TN/TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous operating voltage UC (L-N): 275 VAC
Maximum continuous operating voltage UC (L-PE): 360 VAC
Maximum continuous operating voltage UC (N-PE): 360 VAC
Rated load current IL: 16 A (30°C)
Residual current IPE: ≤ 5 µA
Standby power consumption PC: ≤ 1 VA
Reference test voltage UREF: 255 VAC
Combination wave UOC: 6 kV
Voltage protection level Up: ≤ 1.5 kV
TOV behavior at UT (L-N): 460 VAC (5s / withstand mode)
460 VAC (120min / safe failure mode)
TOV behavior at UT (L-PE): 460 VAC (5s / withstand mode)
460 VAC (120min / withstand mode)
1455 VAC (200ms / safe failure mode)
TOV behavior at UT (N-PE): 1200 VAC (200ms / safe failure mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Response time tA (N-PE): ≤ 100 ns
Max. required back-up fuse: 16 A (gG / B / C)
Short-circuit current rating ISCCR: 1.5 kA AC
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (Child-proofing)
Ambient temperature (operation): -25°C ... 75°C
Ambient temperature (storage/transport): -25°C ... 75°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2019
MountingMounting type: Plugging into the mains socket
Technical Specs
ECLASSECLASS-11.0: 27130806
ECLASS-13.0: 27171203
ETIMETIM 9.0: EC000942
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Flyer_00002.pdf

Flyer_00001.pdf

Manufacturer_declaration_01356.pdf

Manufacturer_declaration_02314.pdf

Manufacturer_declaration_15394.pdf

Package_slip_00338.pdf

Technical_drawing_39141.pdf