Industrial Automation
FL PD 1001 T GT - Ethernet module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Dimensions | Width: 40 mm Height: 100 mm Depth: 109 mm |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Material specifications | Housing material: Metal |
Mounting | Mounting type: DIN rail mounting |
Interfaces | Ethernet (RJ45) Connection method: RJ45 Transmission speed: 10/100/1000 Mbps Transmission physics: Copper Transmission length: 100 m (Total) No. of channels: 1 (RJ45 ports) 1 Ethernet Connection method: RJ45 Transmission speed: 10/100/1000 Mbps Transmission length: up to 100 m (complete system) No. of channels: 1 (RJ45 ports) |
Product properties | Type: Stand-Alone Product type: Power over Ethernet devices Operating mode: Mode transparent MTTF: 1344.41 Years (SN29500 standard, temperature25°C, operating cycle21%) 520.19 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 52.81 Years (SN29500 standard, temperature70°C, operating cycle100%) Insulation characteristics Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Electrical properties | Local diagnostics: 24V Output voltage Green LED PoE PoE detection Yellow LED Test section: for one minute 1500 VAC 1 min. Transmission medium: Copper Supply Supply voltage (DC): 48 VDC (via PoE) Supply voltage range: 44 VDC ... 57 VDC Power supply connection: via PoE |
Connection data | Conductor connection Conductor cross section: 0.14 mm² ... 1.5 mm² Connection cross section AWG: 24 ... 12 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) Vibration (operation): in acc. with IEC 60068-2-6: 5g, 150 Hz Air pressure (operation): 86 kPa ... 108 kPa Air pressure (storage/transport): 66 kPa ... 108 kPa (3500m above sea level) |
EMC data | Conformance with EMC directives: IEC 61000-6-2 IEC 61000-4-2 (ESD) Criterion A IEC 61000-4-3 (immunity to radiated interference) Criterion A IEC 61000-4-4 (burst) Criterion A IEC 61000-4-5 (surge) Criterion A IEC 61000-4-6 (immunity to conducted interference) Criterion A EN 55022 (emitted interference) Criterion A Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-4 |
System properties | Functionality Basic functions: PD, conforms to IEEE 802.3af/at |
Signaling | Status display: LEDs: POE, 24V DC |
ECLASS | ECLASS-11.0: 19170401 ECLASS-12.0: 19170401 ECLASS-13.0: 19170401 |
ETIM | ETIM 9.0: EC000734 |
UNSPSC | UNSPSC 21.0: 43222600 |
Description other products