PHOENIX CONTACT 2900543
PHOENIX CONTACT 2900543
PHOENIX CONTACTAvailable

ELR H3-I-SC- 24DC/500AC-2 - Hybrid motor starter

Hybrid motor starter for starting 3~AC motors up to 500VAC and 2.4A output current, with 24VDC control voltage, adjustable overload shutdown, and screw connection.
Product Code: 2900543
Partner cod.: 2900543
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Hybrid motor starters
Product family: CONTACTRON
Operating mode: 100% operating factor
Electrical propertiesNumber of phases: 3
Motor starter type: Direct starter
Maximum power dissipation for nominal condition: 2.2 W
Switching frequency: ≤ 2 Hz (Load-dependent)
Maximum power dissipation: 3.3 W
Minimum power dissipation: 1.1 W
Coordination type: 1
Supply
Rated control circuit supply voltage US: 24 VDC
Control supply voltage range: 19.2 VDC ... 30 VDC
Rated control supply current IS: 40 mA
Protective circuit: Surge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage: 500 V
Rated surge voltage: 6 kV
Overvoltage category: III
Degree of pollution: 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit: Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC (e.g., 230/400 V AC, 277/480 V AC)
Basic insulation (IEC 60947-1) at operating voltage 300VAC...500VAC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit: Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Input dataControl
Input name: Control input
Rated actuating voltage UC: 24 VDC
Triggering voltage range: 19.2 VDC ... 30 VDC
Rated actuating current IC: 5 mA (Input type 1)
Switching threshold: 9.6 V (“0” signal)
19.2 V (“1” signal)
Typical turn-off time: < 30 ms
Protective circuit: Reverse polarity protection
Output dataAC output
Rated operating voltage Ue: 500 VAC
Operating voltage range: 42 VAC ... 550 VAC
Rated operating current Ie: 2.4 A (AC-51)
2.4 A (AC-53a)
Mains frequency: 50/60 Hz
Load current range: 180 mA ... 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2: Class 10A
Cooling time: 20 min. (for auto reset)
Leakage current: 0 mA
Protective circuit: Surge protection
Acknowledge output
Note: Confirmation: floating change-over contact, signal contact
Contact switching type: 1changeover contact
Switching capacity in accordance with IEC 60947-5-1: 3 A (230 V, AC15)
2 A (24V, DC13)
Connection dataControl circuits
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load circuit
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
SignalingStatus display: Yellow LED
Operating voltage display: Green LED
Error indication: Red LED
DimensionsWidth: 22.5 mm
Height: 107 mm
Depth: 114 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
UL approval
Certificate: NLDX.E228652
UL data
SCCR: 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA: 2.4 A (500 V AC)
Group installation: 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category code: NLDX / NRNT
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-1
IEC 60947-4-2
MountingMounting type: DIN rail mounting
Assembly instructions: alignable, for spacing see derating
Mounting position: vertical (horizontal DIN rail, motor output below)
Technical Specs
ECLASSECLASS-11.0: 27370905
ECLASS-12.0: 27370905
ECLASS-13.0: 27370905
ETIMETIM 9.0: EC001037
UNSPSCUNSPSC 21.0: 25173900
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00061.pdf

Application_note_00064.pdf

Application_note_00062.pdf

Application_note_00076.pdf

Approvals_00051.pdf

Approvals_00052.pdf

Certification_00191.pdf

Data_sheet_03730.pdf

Manufacturer_declaration_00603.pdf

Manufacturer_declaration_02285.pdf

Manufacturer_declaration_15593.pdf

Package_slip_00942.pdf

Technical_drawing_39437.pdf

Other products