Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2901533
PHOENIX CONTACTNot available

RAD-DAIO6-IFS - I/O extension module

Radioline - I/O extension module, 2digital inputs and outputs (0...250VAC/DC) and 1analog input (0/4...20mA) and output (0/4...20mA, 0...10V)
Product Code: 2901533
Partner cod.: 2901533
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Extension module
MTTF: 889 Years (SN29500 standard, temperature25°C, operating cycle21%)
391 Years (SN29500 standard, temperature40°C, operating cycle34.25%)
151 Years (SN29500 standard, temperature40°C, operating cycle100%)
Insulation characteristics
Overvoltage category: II
Degree of pollution: 2
Electrical propertiesElectrical isolation: 300 V (Rated insulation voltage (in each case between the digital inputs // digital outputs //TBUS supply, reinforced insulation in accordance with EN/IEC 61010))
50 V (Rated insulation voltage (in each case between the analog inputs / analog outputs /TBUS supply, reinforced insulation in accordance with EN/IEC 61010))
300 V (Rated insulation voltage (in each case between the digital inputs and outputs // analog inputs and outputs, reinforced insulation in accordance with EN/IEC 61010))
300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN/IEC 61010))
Test voltage for digital I/Os: 2.5 kV AC (50Hz, 1min.)
Test voltage for analog I/Os: 1.5 kV AC (50Hz, 1min.)
Maximum power dissipation for nominal condition: 2.28 W
Transient surge protection: Yes
Supply
Supply voltage range: 19.2 VDC ... 30.5 VDC (DIN rail connector)
Max. current consumption: ≤ 95 mA (At 24 V DC, at 25°C)
Input dataDigital
Max. current consumption: < 1 mA
Analog
Description of the input: Analog input
Number of inputs: 1
Current input signal: 0 mA ... 20 mA (can be set via DIP switches)
4 mA ... 20 mA (can be set via DIP switches)
Max. current input signal: 22 mA
Input resistance current input: < 70 Ω
Resolution: 16 bit
Precision: ≤ 0.02 % (at 25°C)
Protective circuit: Short-circuit and overload protection
Temperature coefficient, typical: typ. 0.0025 %/K (at -40°C ... +70°C)
Supply voltage: 12 VDC (UANA via terminal block PWR1, +I1, for passive sensors, 25mA)
Digital​
Description of the input: Digital input
Number of inputs: 2
Voltage input signal: 0 V AC/DC ... 250 V AC/DC
Switching level "0" signal: 0 V AC/DC ... 4 V AC/DC (Low-voltage input)
0 V AC/DC ... 20 V AC/DC (High-voltage input)
Switching level "1" signal: 10 V AC/DC ... 50 V AC/DC (Low-voltage input)
50 V AC/DC ... 250 V AC/DC (High-voltage input)
Input frequency: ≤ 2 Hz
Output dataDigital
Output name: Relay output
Number of outputs: 2
Contact switching type: Changeover contact
Contact material: AgSnO2
Maximum switching voltage: 250 V AC/DC
Min. switching current: ≥ 10 mA
Max. switching current: 2 A (250VAC)
0.168 A (250VDC)
2 A (24VDC)
Mechanical service life: 1x 107 cycles
Electrical service life: 2x 105 cycles (At 2 A, 250 VAC, cosφ 0.4)
2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency: 2 Hz
Behavior of the outputs (adjustable via DIP switch): Hold / Reset
Analog
Output name: Analog output
Number of outputs: 1
Voltage output signal: 0 V ... 10 V
Max. voltage output signal: ~ 10.83 V
Current output signal: 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal: ~ 21.67 mA
Load: ≥ 10 kΩ
≤ 500 Ω
Resolution: 16 bit
Precision: ≤ 0.02 % (at 25°C)
typ. 0.5 % (Voltage output)
Temperature coefficient, typical: typ. 0.0025 %/K (at -40°C ... +70°C)
Protective circuit: Transient protection of outputs
Connection dataTightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Connection method: Screw connection
Stripping length: 7 mm
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
SignalingStatus display: Green LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)
Yellow LED (digital input, DI1)
Yellow LED (digital input, DI2)
Yellow LED (digital output, DO1)
Yellow LED (digital output, DO2)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2cf50fa12a76e642a87bbf025fee56a1/-S204x204-FJPG
Width: 17.5 mm
Height: 113 mm
Depth: 114.5 mm
Material specificationsMaterial: PA 6.6-FR
Flammability rating according to UL 94: V0
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 70°C (>55°Cderating, see technical documentation)
-40°F ... 158°F (>131°Fderating, see technical documentation)
Ambient temperature (storage/transport): -40°C ... 85°C
-40°F ... 185°F
Altitude: 2000 m
Permissible humidity (operation): 20 % ... 85 %
Permissible humidity (storage/transport): 20 % ... 85 %
Shock: 16g, 11 ms
Vibration (operation): in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
ATEX
Identification:  II 3 G Ex ec nC IIC T4 Gc
Certificate: IBExU15ATEXB008X
Note: Please follow the special installation instructions in the documentation!
IECEx
Identification: Ex ec nC IIC T4 Gc
Certificate: IECExIBE13.0019X
EACEx
Identification: 2Ex nA nC IIC T4 Gc X
Certificate: RU C-DE.HB49.B.00033/20
UL, USA/Canada
Identification: 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
CCC/China-Ex
Identification: Ex ec nC IIC T4 Gc
Certificate: 2022122310115625
KC approval for South Korea
Certificate: R-R-PCK-2901533
Corrosive gas test
Identification: ISA-S71.04-1985 G3 Harsh Group A
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Standards and regulationsStandard designation: EMC Directive 2014/30/EU
Ex Directive (ATEX)
Ex Directive (ATEX)
Standards/specifications: EN61000-6-2
EN61000-6-4
EN60079-0
EN60079-15
MountingAssembly instructions: on standard DIN rail NS 35 in accordance with EN 60715
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27242602
ECLASS-12.0: 27242602
ECLASS-13.0: 27242602
ETIMETIM 9.0: EC001597
UNSPSCUNSPSC 21.0: 32151602
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00172.pdf

Application_note_00171.pdf

Application_note_00205.pdf

Approvals_00172.pdf

Approvals_00173.pdf

Approvals_01193.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01483.pdf

Approvals_01584.pdf

Approvals_01699.pdf

Certification_00243.pdf

Certification_00256.pdf

Data_sheet_03739.pdf

Manual_00120.pdf

Manufacturer_declaration_00677.pdf

Manufacturer_declaration_02119.pdf

Manufacturer_declaration_05544.pdf

Manufacturer_declaration_15639.pdf

Manufacturer_declaration_17707.pdf

Package_slip_02170.pdf

Technical_drawing_39533.pdf

Various_00005.pdf