Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Temperature transmitter Product family: MINI Analog Pro Type: Signal conditioner Configuration: DIP switches Software App Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | Electrical isolation: 3-way isolation Protective circuit: Transient protection Step response (0â99%): 200 ms (2-conductor) 500 ms (3-conductor) 500 ms (4-conductor) Maximum temperature coefficient: 0.01 %/K Transmission error resistance-type sensor: 2é Transmission error resistance thermometer: 0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni) 0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu) Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 3 kV AC (50Hz, 60s) Insulation: Reinforced insulation according to IEC/EN61010-1 Supply Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Typical current consumption: 32 mA (24VDC) 63 mA (12VDC) Power consumption: ⤠850 mW (at IOUT = 20 mA, 9.6 V DC, 600 é load) |
Input data | Signal Number of inputs: 1 Measurement Number of inputs: 1 Configurable/programmable: Yes Sensor types (RTD) that can be used: Pt, Ni, Cu sensors Temperature measuring range: -200°C ... 850°C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches) ⥠20 K Sensor input current: approx. 200 µA Max. permissible overall conductor resistance: ⤠25 é (Per line, RTD in 3- or 4-conductor technology) ⤠50 é (adjustable, RTD in 2-conductor technology) Linear resistance measuring range: 0 é ... 4000 é (Minimum measuring span: 10% of the selected measuring range) Connection technology: 2-, 3-, 4-conductor |
Output data | Signal: Voltage/current Number of outputs: 1 Configurable/programmable: Yes Voltage output signal: 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 10 V (via DIP switch) 10 V ... 0 V (via DIP switch) 0 V ... 10.5 V (can be set via software) Max. voltage output signal: approx. 12.3 V Non-load voltage: < 17.5 V Current output signal: 0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 20 mA ... 4 mA (via DIP switch) 0 mA ... 21 mA (can be set via software) Max. current output signal: 24.6 mA Short-circuit current: < 31.5 mA Load/output load voltage output: ⥠10 ké Load/output load current output: ⤠600 é (at 20 mA) Ripple: < 10 mVrms < 10 mVrms (at 600 é) Resolution, outputs (voltage): 1 mV Resolution, outputs (current): 2 µA Behavior in the event of a sensor error: configurable |
Connection data | Connection method: Screw connection Stripping length: 10 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 (flexible) Tightening torque: 0.5 Nm ... 0.6 Nm |
Ex data | Ex installation (EPL): Gc Div.2 |
Interfaces | Data: IFS interface Connection method: Micro USB type B |
Signaling | Status display: Green LED (supply voltage) Error indication: Red LED |
Dimensions | Width: 6.2 mm Height: 109.81 mm Depth: 119.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 20 ATEX E 024 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF21UKEX2902049X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 20.0017X UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6 Shipbuilding approval Certificate: DNV GL TAA00002UA EACEx Identification: ï 2Ex ec IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00079 DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 0.06 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 0.1 % Surge current load (surge) Standards/regulations: EN61000-4-5 Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 0.07 % |
Standards and regulations | Electrical isolation: 3-way isolation |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |
ECLASS | ECLASS-11.0: 27210129 ECLASS-12.0: 27210129 ECLASS-13.0: 27210129 |
ETIM | ETIM 9.0: EC002919 |
UNSPSC | UNSPSC 21.0: 41112100 |