MINI MCR-2-RTD-UI - Resistance thermometer measuring transducer

Configurable temperature transducer with plug-in connection technology for connecting 2, 3, and 4-conductor resistance thermometers and resistance-type sensors. Configurable via DIP switch or software. Screw connection technology, standard configuration
Product Code: 2902049
Partner cod.: 2902049
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Temperature transmitter
Product family: MINI Analog Pro
Type: Signal conditioner
Configuration: DIP switches
Software
App
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesElectrical isolation: 3-way isolation
Protective circuit: Transient protection
Step response (0–99%): 200 ms (2-conductor)
500 ms (3-conductor)
500 ms (4-conductor)
Maximum temperature coefficient: 0.01 %/K
Transmission error resistance-type sensor: 2Ω
Transmission error resistance thermometer: 0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Electrical isolation Input/output/power supply
Rated insulation voltage: 300 Vrms
Test voltage: 3 kV AC (50Hz, 60s)
Insulation: Reinforced insulation according to IEC/EN61010-1
Supply
Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Typical current consumption: 32 mA (24VDC)
63 mA (12VDC)
Power consumption: ≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Input dataSignal
Number of inputs: 1
Measurement
Number of inputs: 1
Configurable/programmable: Yes
Sensor types (RTD) that can be used: Pt, Ni, Cu sensors
Temperature measuring range: -200°C ... 850°C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches)
≥ 20 K
Sensor input current: approx. 200 µA
Max. permissible overall conductor resistance: ≤ 25 Ω (Per line, RTD in 3- or 4-conductor technology)
≤ 50 Ω (adjustable, RTD in 2-conductor technology)
Linear resistance measuring range: 0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Connection technology: 2-, 3-, 4-conductor
Output dataSignal: Voltage/current
Number of outputs: 1
Configurable/programmable: Yes
Voltage output signal: 0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
10 V ... 0 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Max. voltage output signal: approx. 12.3 V
Non-load voltage: < 17.5 V
Current output signal: 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
20 mA ... 0 mA (via DIP switch)
20 mA ... 4 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. current output signal: 24.6 mA
Short-circuit current: < 31.5 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: ≤ 600 Ω (at 20 mA)
Ripple: < 10 mVrms
< 10 mVrms (at 600 Ω)
Resolution, outputs (voltage): 1 mV
Resolution, outputs (current): 2 µA
Behavior in the event of a sensor error: configurable
Connection dataConnection method: Screw connection
Stripping length: 10 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 1.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12 (flexible)
Tightening torque: 0.5 Nm ... 0.6 Nm
Ex dataEx installation (EPL): Gc
Div.2
InterfacesData: IFS interface
Connection method: Micro USB type B
SignalingStatus display: Green LED (supply voltage)
Error indication: Red LED
DimensionsWidth: 6.2 mm
Height: 109.81 mm
Depth: 119.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: BVS 20 ATEX E 024 X
UKCAEx(UKEX)
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: PxCIF21UKEX2902049X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx BVS 20.0017X
UL, USA/Canada
Identification: UL508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Shipbuilding approval
Certificate: DNV GL TAA00002UA
EACEx
Identification:  2Ex ec IIC T4 Gc
Certificate: BY/112 02.01 TP012 103.01 00079
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Comments: Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 0.06 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 0.1 %
Surge current load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 0.07 %
Standards and regulationsElectrical isolation: 3-way isolation
MountingMounting type: DIN rail mounting
Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail.
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210129
ECLASS-12.0: 27210129
ECLASS-13.0: 27210129
ETIMETIM 9.0: EC002919
UNSPSCUNSPSC 21.0: 41112100
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00128.pdf

Approvals_00172.pdf

Approvals_00173.pdf

Approvals_01457.pdf

Approvals_01460.pdf

Approvals_01500.pdf

Data_sheet_03762.pdf

Manual_00026.pdf

Manufacturer_declaration_00749.pdf

Manufacturer_declaration_01722.pdf

Manufacturer_declaration_15690.pdf

Manufacturer_declaration_17788.pdf

Manufacturer_declaration_17795.pdf

Package_slip_01624.pdf

Product_information_00033.pdf

Product_information_00562.pdf

Technical_drawing_39608.pdf