Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2902056
PHOENIX CONTACTNot available

MINI MCR-2-F-UI - Frequency measuring transducer

Universally configurable frequency transducer for converting frequency (Hz/rpm) and PWM signals into standard signals. Sensor voltages greater than 8.2VDC are possible in combination with MINI MCR-2-SPS 1033202. Screw connection technology.
Product Code: 2902056
Partner cod.: 2902056
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Frequency value transformer
Product family: MINI Analog Pro
No. of channels: 1
Type: Signal conditioner
Configuration: DIP switches
Software
App
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
System propertiesFunctionality
Configuration: DIP switches
Software
App
Electrical propertiesNo. of channels: 1
Step response (0–99%): < 35 ms (f > 500Hz)
Maximum temperature coefficient: 0.01 %/K
Maximum transmission error: 0.1 % (Frequency (Hz/rpm))
1 % (PWM signal)
Electrical isolation Input/output/power supply
Rated insulation voltage: 300 Vrms
Test voltage: 3 kV AC (50Hz, 60s)
Insulation: Reinforced insulation according to IEC/EN61010-1
Supply
Nominal supply voltage: 24 VDC
Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Typical current consumption: 32 mA (24VDC)
63 mA (12VDC)
Power consumption: ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Input dataMeasurement: Frequency
Available input sources: NAMUR initiators
NPN/PNP transistor outputs
Floating contact (dry contact)
Frequency generator
Incremental encoder (speed only)
HTL encoders
TTL rotary transducer
S0 signal
Max. voltage input signal: 30 V (incl. DC voltage)
Voltage measuring range: ≥ 2 V
Frequency measuring range: 0.002 Hz ... 200 kHz
PWM (range): 0.002 Hz ... 60 Hz (Duty cycle 2...98%)
60 Hz ... 300 Hz (Duty cycle: 5...95%)
300 Hz ... 600 Hz (Duty cycle: 10...90%)
600 Hz ... 1000 Hz (Duty cycle 20...80%)
Signal
Number of inputs: 1
Input signal: Frequency
Output dataSwitching: Transistor
Number of outputs: 1
Contact switching type: 1 N/O contact
Minimum switching voltage: 1 V
Maximum switching voltage: 30 VDC
Min. switching current: 100 µA
Max. switching current: 100 mA (30V)
Signal: Voltage/current
Number of outputs: 1
Configurable/programmable: Yes
Voltage output signal: 0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Max. voltage output signal: 12.3 V
Current output signal: 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. current output signal: 24.6 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: ≤ 600 Ω (20mA)
Ripple: < 20 mVPP (600Ω)
Connection dataConnection method: Screw connection
Stripping length: 10 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 1.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12 (flexible)
Tightening torque: 0.5 Nm ... 0.6 Nm
Ex dataEx installation (EPL): Gc
Div.2
SignalingStatus display: Green LED (supply voltage)
Yellow LED (switching output)
Error indication: Red LED
DimensionsWidth: 6.2 mm
Height: 109.81 mm
Depth: 119.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: BVS 20 ATEX E 024 X
UKCAEx(UKEX)
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: PxCIF21UKEX2902049X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx BVS 20.0017X
UL, USA/Canada
Identification: UL508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
Shipbuilding approval
Certificate: DNV GL TAA000021E Rev. 1
EACEx
Identification:  2Ex ec IIC T4 Gc
Certificate: BY/112 02.01 TP012 103.01 00081
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Comments: Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 0.2 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 0.1 %
Surge current load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 2.8 %
MountingMounting type: DIN rail mounting
Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail.
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210128
ECLASS-12.0: 27210128
ECLASS-13.0: 27210128
ETIMETIM 9.0: EC002918
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00128.pdf

Approvals_00172.pdf

Approvals_00173.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01460.pdf

Approvals_01500.pdf

Approvals_01944.pdf

Data_sheet_03764.pdf

Manual_00026.pdf

Manufacturer_declaration_01011.pdf

Manufacturer_declaration_01808.pdf

Manufacturer_declaration_15693.pdf

Manufacturer_declaration_17788.pdf

Manufacturer_declaration_17795.pdf

Package_slip_01613.pdf

Product_information_00033.pdf

Technical_drawing_39611.pdf