Industrial Automation
MINI MCR-SL-CVS-24-5-10-NC - Constant voltage source
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Constant voltage source Product family: MINI Analog Configuration: DIP switches Insulation characteristics Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches |
Electrical properties | Setting range comparison: ± 300 mV Maximum power dissipation for nominal condition: 300 mW Maximum temperature coefficient: < 0.01 %/K Temperature coefficient, typical: < 0.002 %/K Maximum transmission error: ⤠0.1 % (of final value) ⤠0.5 % (Without adjustment) Electrical isolation Input/output Rated insulation voltage: 50 V AC/DC Test voltage: 1.5 kV AC (50Hz, 60s) Insulation: Basic insulation in accordance with IEC/EN61010 Supply Nominal supply voltage: 24 VDC Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Max. current consumption: < 25 mA (10V output with 30mA load at 24V DC IN) < 65 mA (10V output with 30mA load at 9.6V DC IN) < 50 mA (10V voltage output with 30 mA load at 12V DC IN) < 20 mA (10V voltage output with 30 mA load at 30V DC IN) Power consumption: < 600 mW (at 24 V IN) < 624 mW (at 9.6 V IN) < 564 mW (At 12 V IN) < 540 mW (at 30 V IN) |
Input data | Signal: Voltage Voltage input signal: 9.6 VDC ... 30 VDC |
Output data | Signal: Voltage Configurable/programmable: Yes, preconfigured Max. voltage output signal: 10 VDC 7.5 VDC 5 VDC 2.5 VDC Short-circuit current: approx. 32 mA Output current: ⤠30 mA Ripple: < 20 mVPP |
Connection data | Connection method: Screw connection Stripping length: 12 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 26 ... 12 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG Width: 6.2 mm Height: 93.1 mm Depth: 101.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 65°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC Shipbuilding approval Certificate: DNV GL TAA00002R0 DNV GL data Temperature: B Humidity: B Vibration: B EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 3 % Electromagnetic HF fieldâ Comments: Criterion A Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 3 % Fast transients (burst)â Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Comments: Criterion B Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 0.5 % Conducted interferenceâ Comments: Criterion A |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |
ECLASS | ECLASS-11.0: 27040701 ECLASS-12.0: 27040701 ECLASS-13.0: 27210192 |
ETIM | ETIM 9.0: EC002498 |
UNSPSC | UNSPSC 21.0: 39121000 |