Industrial Automation
Input data | AC operation Network type: Star network Nominal input voltage range: 3x 400 VAC ... 500 VAC Input voltage range: 3x 400 VAC ... 500 VAC -20%...+15% Typical national grid voltage: 3x 400 VAC 3x 480 VAC Voltage type of supply voltage: AC Inrush current integral (I2t): ⤠1.1 A2s Inrush current limitation: 35 A (after 1ms) AC frequency range: 50 Hz ... 60 Hz Frequency range (fN): 50 Hz ... 60 Hz ±5Hz Mains buffering time: > 10 ms (400VAC) > 20 ms (480VAC) Current consumption: 3x 1.9 A (400VAC) 3x 1.7 A (500 VAC) Nominal power consumption: 1335.1 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.77 Typical response time: < 1 s Input fuse: 6.3 A (internal (device protection)) Recommended breaker for input protection: 10 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA < 2.5 mA (550 V AC, 60 Hz) POWER factor: > 0.7 (400VAC) > 0.7 (480VAC) |
Output data | Efficiency: typ. 93 % (400VAC) typ. 93.3 % (480VAC) Output characteristic: U/I with dynamic load reserve Nominal output voltage: 24 VDC ±1% Setting range of the output voltage (USet): 24 VDC ... 28 VDC (> 24 VDC, constant capacity restricted) Nominal output current (IN): 40 A Dynamic Boost (IDyn.Boost): 60 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) POWER factor: > 0.7 (400VAC) > 0.7 (480VAC) Feedback voltage resistance: < 35 V Protection against overvoltage at the output (OVP): ⤠30 VDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %) Residual ripple: ⤠50 mVPP Short-circuit-proof: yes No-load proof: yes Output power: 960 W 1440 W Maximum no-load power dissipation: typ. 14 W (400VAC) typ. 17 W (480VAC) Power loss nominal load max.: < 70 W (480VAC) typ. 72 W (480VAC) Short-circuit current: < 48 ADC (Permanent) Rise time: ⤠1 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK Continuous load current: 100 mA Signal relay 13/14 Default: closed Digital: 30 VAC 30 VDC 100 mA |
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.75 mm² Conductor cross section, rigid max.: 16 mm² Conductor cross section flexible min.: 0.75 mm² Conductor cross section flexible max.: 10 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.75 mm² Single conductor/terminal point, stranded, with ferrule, max.: 10 mm² Conductor cross section AWG min.: 20 Conductor cross section AWG max.: 4 Stripping length: 18 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm² Single conductor/terminal point, stranded, with ferrule, max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Signaling | Types of signaling: LED Floating signal contact Signal output: LED status indicator Signalization designation: DC OK Status display: LED Color: green DC OK: UOUT > 0.9 x UN (UN = 24VDC) |
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 3 kV AC (type test) 1.5 kV AC (routine test) |
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 1730000 h (25°C) > 1051000 h (40°C) > 510000 h (60°C) Insulation characteristics Protection class: I (in closed control cabinet) Degree of pollution: 2 |
Dimensions | Width: 110 mm Height: 130 mm Depth: 160 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (⤠40°C) 10 mm (⤠70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Type of housing: Aluminum (AlMg3) Hood version: Polycarbonate |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ⤠4000 m (>2000m, Derating: 10%/1000m) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock: 11ms, 15g, in each space direction (according to IEC 60068-2-27) Vibration (operation): DNVGL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 13.2 Hz, ±1 mm amplitude, 13.2 Hz - 100 Hz, 0.7g acceleration |
Standards and regulations | Rail applications: EN50121-4 Standard â Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV) Standard â Limitation of mains harmonic currents: EN61000-3-2 Standard - Electrical safety: IEC 62368-1(SELV) Standard â Safety extra-low voltage: IEC 62368-1 (SELV) und EN60204-1 (PELV) Standard - Safe isolation: DINVDE0100-410 Standard - Safety of power supply units up to 1100 V (insulation distances): DINEN61558-2-16 Overvoltage category EN 60950-1: II EN 62477-1: III |
Approvals | UL approvals: UL Listed UL508 UL/C-UL Recognized UL60950-1 Conformity/Approvals SIL in accordance with IEC 61508: 0 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: EN61000-6-3 EN61000-6-4 EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN55016 EN61000-6-3 (Class B) Noise emission: EN 55011 (EN 55022) EN55016 EN61000-6-3 (Class B) Harmonic currents Frequency range: Class A, B Flicker Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 3 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 3 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: EN61000-4-11 Voltage: 230 VAC Frequency: 50 Hz Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
ECLASS | ECLASS-11.0: 27040701 ECLASS-13.0: 27040701 ECLASS-12.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products