TRIO-PS-2G/1AC/12DC/10 - Power supply unit


Input data | AC operation Network type: Star network Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 100 VÃAC ... 240 VÃAC -15Ã%Ã...Ã+10Ã% Input voltage range AC: 85 VÃAC ... 264 VÃAC Electric strength, max.: ââ°¤ 300 VÃAC 15 s Typical national grid voltage: 120 VÃAC 230 VÃAC Voltage type of supply voltage: AC/DC Inrush current: ââ°¤ 30 A (typical) Inrush current integral (I2t): < 1.5 A2s Inrush current limitation: typ. 30 A (after 1Ãms) AC frequency range: 50 Hz ... 60 Hz ñ10Ã% Mains buffering time: typ. 20 ms (120ÃVÃAC) typ. 20 ms (230 V AC) Current consumption: 2.2 A (100ÃVÃAC) 1.9 A (120ÃVÃAC) 1.1 A (230 V AC) 1.1 A (240ÃVÃAC) Nominal power consumption: 254.7 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.53 Typical response time: < 1 s Input fuse: 6.3 A Fast blow (internal (device protection)) Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 0.25 mA DC operation Nominal input voltage range: 122 VÃDC ... 250 VÃDC Input voltage range: 122 VÃDC ... 275 VÃDC Extended input voltage range in operation: > 106 VÃAC Derating: < 99 VÃDC (2 %/V) Shut-down voltage: 105 VÃDC Voltage type of supply voltage: AC/DC Mains buffering time: > 100 ms (230 V AC) Current consumption: 1.4 A (122ÃVÃDC) 0.6 A (250ÃVÃDC) |
Output data | Efficiency: typ. 87.5 % (120ÃVÃAC) typ. 88.7 % (230 V AC) Output characteristic: U/I with dynamic load reserve Nominal output voltage: 12 VÃDC ñ1Ã% Setting range of the output voltage (USet): 12 VÃDC ... 18 VÃDC (> 12 VÃDC, constant capacity restricted) Nominal output current (IN): 10 A Dynamic Boost (IDyn.Boost): 15 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) Feedback voltage resistance: < 25 V Protection against overvoltage at the output (OVP): ââ°¤ 22 VÃDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 50 mVPP (with nominal values) Output power: 120 W 180 W Maximum no-load power dissipation: < 1 W (230ÃV) Power loss nominal load max.: < 15 W (230ÃV) Rise time: ââ°¤ 10 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK Maximum switching voltage: 30 V AC/DC Continuous load current: 100 mA |
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 8 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Signaling | Types of signaling: LED Floating signal contact Signal output: LED status indicator Signalization designation: DC OK Status display: ââ¬Ã DC OKâ⬠LED Color: green |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 3 kV AC (type test) 1.5 kV AC (routine test) |
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > (25ðC) > 1700000 h (40ðC) 60ðC Insulation characteristics Protection class: II (in closed control cabinet) Degree of pollution: 2 |
Dimensions | Width: 35 mm Height: 130 mm Depth: 115 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (ââ°¤ 40°C) 10 mm (ââ°¤ 70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Plastic PC Type of housing: Polycarbonate Hood version: Polycarbonate |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -25°C Maximum altitude: ââ°¤ 5000 m (>Ã2000Ãm, Derating: 10Ã%/1000Ãm) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 4g, 90 min. |
Standards and regulations | Rail applications: ENÃ50121-4 Standard ââ¬Ã¢ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÃ50178/VDEÃ0160 (PELV) Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 62368-1Ã(SELV) Standard ââ¬Ã¢ Safety extra-low voltage: IEC 60950-1 (SELV) and ENÃ60204-1 (PELV) Standard - Safe isolation: DINÃVDEÃ0100-410 Standard - Safety of transformers: ENÃ61558-2-16 (air clearances and creepage distances only) |
Approvals | UL approvals: UL Listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 Conformity/Approvals SIL in accordance with IEC 61508: 0 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 3 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 3 kV (Test Level 4 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 230 VÃAC Frequency: 50 Hz Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |