Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2903908
PHOENIX CONTACT 2903908
PHOENIX CONTACTNot available

ELR H5-I-PT- 24DC/500AC-0,6 - Hybrid motor starter

Hybrid motor starter for reversing 3~AC motors up to 500VAC and 0.6A output current, with 24VDC control voltage, adjustable overload shutdown, and push-in connection.
Product Code: 2903908
Partner cod.: 2903908
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral: If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board.
Product propertiesProduct type: Hybrid motor starters
Product family: CONTACTRON
Operating mode: 100% operating factor
Electrical propertiesNumber of phases: 3
Motor starter type: Reversing starter
Maximum power dissipation for nominal condition: 0.4 W
Switching frequency: ≤ 2 Hz (Load-dependent)
Maximum power dissipation: 1.5 W
Minimum power dissipation: 1.1 W
Coordination type: 1
Supply
Rated control circuit supply voltage US: 24 VDC
Control supply voltage range: 19.2 VDC ... 30 VDC
Rated control supply current IS: 40 mA
Protective circuit: Surge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage: 500 V
Rated surge voltage: 6 kV
Overvoltage category: III
Degree of pollution: 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit: Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC (e.g., 230/400 V AC, 277/480 V AC)
Basic insulation (IEC 60947-1) at operating voltage 300VAC...500VAC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit: Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Input dataControl
Input name: Control input right/left
Rated actuating voltage UC: 24 VDC
Triggering voltage range: 19.2 VDC ... 30 VDC
Rated actuating current IC: 5 mA (Input type 1)
Switching threshold: 9.6 V (“0” signal)
19.2 V (“1” signal)
Typical turn-off time: < 30 ms
Protective circuit: Reverse polarity protection
Output dataAC output
Rated operating voltage Ue: 500 VAC
Operating voltage range: 42 VAC ... 550 VAC
Rated operating current Ie: 0.6 A (AC-51)
0.6 A (AC-53a)
Mains frequency: 50/60 Hz
Load current range: 75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2: Class 10A
Cooling time: 20 min. (for auto reset)
Leakage current: 0 mA
Protective circuit: Surge protection
Acknowledge output
Note: Confirmation: floating change-over contact, signal contact
Contact switching type: 1changeover contact
Switching capacity in accordance with IEC 60947-5-1: 3 A (230 V, AC15)
2 A (24V, DC13)
Connection dataControl circuits
Connection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Load circuit
Connection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
SignalingStatus display: Yellow LED
Operating voltage display: Green LED
Error indication: Red LED
DimensionsWidth: 22.5 mm
Height: 107.5 mm
Depth: 114 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
UL approval
Certificate: NLDX.E228652
UL data
SCCR: 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA: 0.6 A (500 V AC)
Group installation: 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category code: NLDX / NRNT
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-1
IEC 60947-4-2
MountingMounting type: DIN rail mounting
Assembly instructions: alignable, for spacing see derating
Mounting position: vertical (horizontal DIN rail, motor output below)
Technical Specs
ECLASSECLASS-11.0: 27370905
ECLASS-12.0: 27370905
ECLASS-13.0: 27370905
ETIMETIM 9.0: EC001037
UNSPSCUNSPSC 21.0: 25173900
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00061.pdf

Application_note_00076.pdf

Approvals_00051.pdf

Approvals_00052.pdf

Data_sheet_03734.pdf

Manufacturer_declaration_00603.pdf

Manufacturer_declaration_02285.pdf

Manufacturer_declaration_15888.pdf

Package_slip_00957.pdf

Technical_drawing_39898.pdf