PHOENIX CONTACT 2904612
PHOENIX CONTACT 2904612
PHOENIX CONTACTNot available

QUINT4-PS/1AC/48DC/20 - Power supply unit

QUINT POWER primary-switched power supply with free choice of output characteristic curve, SFB(Selective Fuse Breaking) Technology, and NFC interface, input: 1-phase, output:48VDC/20A
Product Code: 2904612
Partner cod.: 2904612
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataControl input (configurable) Rem: Output power ON/OFF (SLEEP MODE)
Default: Output power ON (>40kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type: Star network
Nominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 100 VAC ... 240 VAC -15%...+10%
Electric strength, max.: 300 VAC 60 s
Typical national grid voltage: 120 VAC
230 VAC
Voltage type of supply voltage: AC/DC
Inrush current: typ. 12 A (at 25°C)
Inrush current integral (I2t): < 1 A2s
Inrush current limitation: 12 A (after 1ms)
Frequency range (fN): 50 Hz ... 60 Hz -10%...+10%
16.7 Hz (acc. to EN50163)
Mains buffering time: typ. 27 ms (120VAC)
typ. 28 ms (230 V AC)
Current consumption: 13.6 A (100VAC)
5.4 A (240VAC)
Input fuse: 16 A (slow-blow, internal)
Recommended breaker for input protection: 16 A ... 20 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
1.7 mA (264VAC, 60Hz)
DC operation
Nominal input voltage range: 110 VDC ... 250 VDC
Input voltage range: 110 VDC ... 250 VDC -18%...+40%
Voltage type of supply voltage: DC
Current consumption: 12 A (110VDC)
5 A (250VDC)
Output dataEfficiency: typ. 95.2 % (120VAC)
typ. 96.2 % (230 V AC)
Nominal output voltage: 48 VDC
Setting range of the output voltage (USet): 48 VDC ... 56 VDC (constant capacity)
Nominal output current (IN): 20 A
Static Boost (IStat.Boost): 22.5 A
Dynamic Boost (IDyn.Boost): 30 A (5 s)
Selective Fuse Breaking (ISFB): 105 A (15 ms)
Magnetic circuit breaker tripping: A1...A20 / B2...B10 / C1...C6 / Z1...Z16
Derating: > 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 60 VDC
Protection against overvoltage at the output (OVP): ≤ 60 VDC
Control deviation: < 0.5 % (Static load change 10% ... 90%)
< 1 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple: < 50 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 960 W
1080 W
1440 W
Maximum no-load power dissipation: < 4 W (120VAC)
< 4 W (230 V AC)
Power loss nominal load max.: < 51 W (120VAC)
< 41 W (230 V AC)
Power dissipation SLEEP MODE: < 3 W (120VAC)
< 3 W (230 V AC)
Crest factor: typ. 1.66 (120VAC)
typ. 1.63 (230 V AC)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal
Signal ground SGnd: Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital: 0 VDC 24 VDC 20 mA
Default: 24 VDC 20 mA 24VDC for UOut >0.9xUSet
Signal Out 2 (configurable)
Digital: 0 VDC 24 VDC 20 mA
Analog: 4 mA ... 20 mA ±5% (Load ≤400Ω)
Default: 24 VDC 20 mA 24VDC for POut<PN
Signal relay 13/14 (configurable)
Default: closed (Uout > 0.9 USet)
Digital: 24 VDC 1 A
30 V AC/DC 0.5 A
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 16 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 16 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 6
Stripping length: 10 mm
Tightening torque, min: 1.2 Nm
Tightening torque max: 1.5 Nm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut: > 100% (LED lights up yellow, output power > 960W)
> 75% (LED lights up green, output power > 720W)
> 50% (LED lights up green, output power > 480W)
UOut: > 0.9xUSet (LED lights up green)
< 0.9xUSet (LED flashes green)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE: 2.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency: 85 kHz ... 107 kHz (Auxiliary converter stage)
45 kHz ... 200 kHz (Main converter stage)
50 kHz ... 500 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 949000 h (25°C)
> 569000 h (40°C)
> 260000 h (60°C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 10 A
Temperature: 40°C
Time: 367000 h
Additional text: 120VAC
Life expectancy (electrolytic capacitors)​
Current: 10 A
Temperature: 40°C
Time: 452000 h
Additional text: 230VAC
Life expectancy (electrolytic capacitors)​​
Current: 20 A
Temperature: 25°C
Time: 440000 h
Additional text: 120VAC
Life expectancy (electrolytic capacitors)​​​
Current: 20 A
Temperature: 25°C
Time: 614000 h
Additional text: 230VAC
Life expectancy (electrolytic capacitors)​​​​
Current: 20 A
Temperature: 40°C
Time: 155000 h
Additional text: 120VAC
Life expectancy (electrolytic capacitors)​​​​​
Current: 40 A
Temperature: 40°C
Time: 217000 h
Additional text: 230VAC
DimensionsWidth: 120 mm
Height: 130 mm
Depth: 140 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail: 35 mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 11ms, 15g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5Hz ... 100Hz resonance search 0.7g, 90min., resonance frequency 0.7g, 90min. (in accordance with DNV GL Class A)
Standards and regulationsRail applications: EN50121-3-2
EN50121-5
IEC 62236-3-2
IEC 62236-5
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 61010-2-201(SELV)
Standard – Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - Safety of transformers: EN61558-2-16
Battery charging: DIN41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIF47-0706, EN61000-4-11
Overvoltage category
EN 61010-1: II(≤5000m)
EN 62477-1: III(≤2000m)
EN61558-2-16: II(≤4000m)
ApprovalsCSA: CAN/CSA-C22.2 No.61010-2-201
CAN/CSA-C22.2 No.107.1-16
Shipbuilding approval: DNV applied for
SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals: UL Listed UL508
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: IEC 61850-3
EN61000-6-5
Conducted noise emission: EN55016
EN61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
EN55016
EN61000-6-3 (Class B)
DNVGL conducted interference: ClassA
Additional text: Area power distribution
Bridge and deck area
DNVGL noise radiation: ClassB
Harmonic currents
Standards/regulations: EN61000-3-2
EN61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: typ. 2 kV (Test Level 4 - symmetrical)
typ. 4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 16.7 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: EN61000-4-11
Voltage: 230 VAC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 0.5 / 1 / 25 / 30 periods
5 / 10 / 50 periods
0,5 / 1 / 5 / 50 / 250 periods
Additional text: Test Level 2
Comments: Criterion A
Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations: EN61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: EN61000-4-12
Input: 1 kV (Test Level 4 - symmetrical)
2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: EN61000-4-16
Test level 1: 15 Hz 150 Hz (Test Level 4)
Voltage: 30 V 3 V
3 V
3 V 30 V
30 V
30 V (10s)
30 V (Permanent)
300 V (1 s)
Test level 2: 150 Hz 1.5 kHz (Test Level 4)
Test level 3: 1.5 kHz 15 kHz (Test Level 4)
Test level 4: 15 kHz 150 kHz (Test Level 4)
Test level 5: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Test level 6: 150 Hz 180 Hz (Test Level 4)
Test level 7: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: EN61000-4-18
Input, output (test level1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage: 1 kV
2.5 kV
1 kV
2.5 kV
Input, output (test level2): 10 MHz (Test Level 3 - asymmetrical)
Input, output (test level3): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Signals (test level1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Signals (test level2): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Comments: Criterion A
Attenuated oscillating magnetic field
Standards/regulations: EN61000-4-10
Test field strength: 100 A/m
Test level 1: 100 kHz
Test level 2: 1 MHz
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03843.pdf

Manufacturer_declaration_03311.pdf

Manufacturer_declaration_03312.pdf

Manufacturer_declaration_15951.pdf

Package_slip_02134.pdf

Technical_drawing_39984.pdf

Various_00006.pdf