Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2905153
PHOENIX CONTACT 2905153
PHOENIX CONTACTNot available

ELR H5-IES-SC/500AC-9-IFS - Hybrid motor starter

Networkable hybrid motor starter for reversing 3~AC motors up to 500VAC and 9A output current, with adjustable overload shutdown, emergency stop function up to SIL3/PLe, and screw connection, DIN rail connector provided.
Product Code: 2905153
Partner cod.: 2905153
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Hybrid motor starters
Product family: CONTACTRON
Operating mode: 100% operating factor
Electrical propertiesNumber of phases: 3
Motor starter type: Reversing starter
Maximum power dissipation for nominal condition: 12 W
Switching frequency: ≤ 2 Hz (Load-dependent)
Maximum power dissipation: 7 W
Minimum power dissipation: 0.88 W
Coordination type: 1
Supply
Rated control circuit supply voltage US: 24 VDC
Control supply voltage range: 19.2 VDC ... 30 VDC
Rated control supply current IS: 60 mA
Protective circuit: Surge protection
Reverse polarity protection; Parallel polarity protection diode
Insulation characteristics
Rated insulation voltage: 550 V
Rated surge voltage: 6 kV
Overvoltage category: III
Degree of pollution: 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit: Safe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuit: Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Emergency tripping
Operate threshold: > 60 A
Response time: < 0.5 s
Input dataControl
Input name: Enable input
Note: The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3ms duration),
unblanking pulses of max. 4ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC: 24 VDC
Triggering voltage range: 19.2 VDC ... 30 VDC
Rated actuating current IC: 7 mA
Switching threshold: 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level: < 5 VDC (For EMERGENCY STOP)
Typical turn-off time: < 30 ms
Protective circuit: Reverse polarity protection
Output dataAC output
Rated operating voltage Ue: 500 VAC
Operating voltage range: 42 VAC ... 550 VAC
Rated operating current Ie: 9 A (AC-51)
7 A (AC-53a)
Mains frequency: 50/60 Hz
Load current range: 1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2: Class 10A
Cooling time: 20 min. (for auto reset)
Leakage current: 0 mA
Protective circuit: Surge protection; Varistor
Connection dataControl circuits
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load circuit
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
SignalingStatus display: Yellow LED
Operating voltage display: Green LED
Error indication: Red LED
DimensionsWidth: 22.5 mm
Height: 107 mm
Depth: 114 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -5°C ... 60°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
ATEX
Identification:  II (2) G [Ex eb] [Ex db] [Ex pxb]
 II (2) D [Ex tb] [Ex pb]
Certificate: PTB 15 ATEX 3000
UL approval
Certificate: NLDX.E228652
NRNT.E172140
Safety Integrity Level (SIL, IEC 61508)
Identification: ≤3
Note: Safe shutdown
Safety Integrity Level (SIL, IEC 61508)​
Identification: 2
Note: Motor protection
Performance Level (ISO13849)
Identification: e
Note: Safe shutdown
Category (ISO13849)
Identification: ≤3
Note: Safe shutdown
UL data
SCCR: 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA: 7.6 A (480VAC)
Group installation: 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category code: NLDX / NRNT
Horsepower ratings: 2 hp (208VAC)
2 hp (230 V AC)
2 hp (240VAC)
5 hp (480VAC)
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-1
EN60947-4-2
IEC 61508
ISO13849
MountingMounting type: DIN rail mounting
Assembly instructions: alignable, for spacing see derating
Mounting position: vertical (horizontal DIN rail, motor output below)
Technical Specs
ECLASSECLASS-11.0: 27370905
ECLASS-13.0: 27370905
ECLASS-12.0: 27370905
ETIMETIM 9.0: EC001037
UNSPSCUNSPSC 21.0: 25173900
Description
Networkable hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 9 A output current, with adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and screw connection, DIN rail connector provided.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Application_note_00076.pdf

Approvals_00051.pdf

Approvals_00052.pdf

Approvals_01380.pdf

Data_sheet_03868.pdf

Manufacturer_declaration_00822.pdf

Manufacturer_declaration_01954.pdf

Manufacturer_declaration_16001.pdf

Package_slip_00959.pdf

Technical_drawing_40076.pdf