PHOENIX CONTACT 2905339
PHOENIX CONTACT 2905339
PHOENIX CONTACTNot available

VAL-SEC-T2-3C-350-FM - Type 2 surge arrester

Plug-in surge arrester, in accordance with Type 2/Class II, for 3-phase power supply networks with combined PE and N installed in one conductor (4-conductor system: L1, L2, L3, PEN), with remote indication contact.
Product Code: 2905339
Partner cod.: 2905339
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: TN-C
Type: DIN rail module, two-section, divisible
Product type: Surge arrester
Product family: SEC Family
Number of positions: 3
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 5 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 5 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 16 mm
Conductor cross section flexible: 2.5 mm² ... 16 mm²
1.5 mm² ... 6 mm²
Conductor cross section rigid: 2.5 mm² ... 25 mm²
Conductor cross section AWG: 12 ... 4
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d55cb695c9e2114cae6c227cd8756a59/-S204x204-FJPG
Width: 37.3 mm
Height: 97.9 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 2 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: L-PEN
Direction of action: 3L-N/PE
Nominal voltage UN: 240/415VAC (TN-C)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 350 VAC
Rated load current IL: 40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Short-circuit current rating ISCCR: 25 kA (for a backup fuse of up to 315AgG)
50 kA (for a backup fuse of up to 200AgG)
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT: 415 VAC (5s / withstand mode)
457 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring: 315 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV (L-L): 700 VAC
Maximum continuous operating voltage MCOV (L-N): 350 VAC
Nominal discharge current In (L-L): 20 kA
Nominal discharge current In (L-N): 20 kA
Mode of protection: L-L
L-N
Nominal voltage: 277/480VAC
Power distribution system: Wye
Nominal frequency: 50/60 Hz
Measured limiting voltage MLV (L-L): 3280 V
Measured limiting voltage MLV (L-N): 2000 V
SPD Type: 4CA
UL indicator/remote signaling
Operating voltage: 125 VAC
AC operating current: 1 A AC
UL connection data
Tightening torque: 40 lbf-in. ... 50 lbf-in.
Conductor cross section AWG: 14 ... 2 (solid)
14 ... 4 (flexible)
Standards and regulationsAir clearances and creepage distances
Standards/regulations: DINVDE0110-1 / IEC 60664-1 / IEC 61643-11
Standards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130805
ECLASS-13.0: 27171202
ETIMETIM 9.0: EC000941
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_00343.pdf

Approvals_00390.pdf

Approvals_01875.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Flyer_00003.pdf

Manufacturer_declaration_00786.pdf

Manufacturer_declaration_02098.pdf

Package_slip_00563.pdf

Product_information_00033.pdf

Product_information_00152.pdf

Product_information_00666.pdf

Technical_drawing_40117.pdf