PHOENIX CONTACT 2905469
PHOENIX CONTACTNot available

FLT-SEC-T1+T2-3C-350/25-FM - Type 1+2 special combined lightning current and surge arrester

Plug-in lightning and surge arrester combination, in accordance with Type 1+2/Class I+II, for 3-phase power supply networks, with combined PE and N installed in one conductor (L1, L2, L3, PEN).
Product Code: 2905469
Partner cod.: 2905469
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I + II
T1 + T2
EN type: T1 + T2
IEC power supply system: TN-C
Type: DIN rail module, two-section, divisible
Product type: Arrester combination
Product family: SEC Family
Number of positions: 3
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 12 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 10 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 18 mm
Conductor cross section flexible: 2.5 mm² ... 35 mm²
1.5 mm² ... 16 mm²
Conductor cross section rigid: 2.5 mm² ... 35 mm²
Conductor cross section AWG: 13 ... 2
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e6787c2b5836404db1ade35ac965e0ab/-S204x204-FJPG
Width: 106.8 mm
Height: 95.2 mm
Depth: 74.5 mm
Horizontal pitch: 6 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-PEN
Direction of action: 3L-N/PE
Nominal voltage UN: 240/415VAC (TN-C)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 350 VAC
Rated load current IL: 125 A (< 55°C)
Nominal discharge current In (8/20) µs: 25 kA
Impulse discharge current (10/350)µs, charge: 12.5 As
Impulse discharge current (10/350)µs, specific energy: 160 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 25 kA
Follow current interrupt rating Ifi: 25 kA (264 V AC)
3 kA (350 V AC)
Short-circuit current rating ISCCR: 25 kA (264 VAC)
3 kA (350 V AC)
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 1.5 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
TOV behavior at UT: 415 VAC (5s / withstand mode)
457 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 125 A (gG)
Max. backup fuse with branch wiring: 315 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 100 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV (L-L): 528 VAC
Maximum continuous operating voltage MCOV (L-G): 264 VAC
Short-circuit current rating (SCCR): 50 kA
Voltage protection rating VPR (L-L): 2000 V
Voltage protection rating VPR (L-G): 1200 V
Nominal discharge current In: 20 kA
Mode of protection: L-L
L-G
Nominal voltage: 240VAC
240/415VAC
Rated load current IL: 50 A
Power distribution system: Delta
Wye
Nominal frequency: 50/60 Hz
SPD Type: 2CA
UL indicator/remote signaling
Operating voltage: 125 VAC
AC operating current: 1 A AC
UL connection data
Tightening torque: 40 lbf-in.
Conductor cross section AWG: 3 ... 2
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130808
ECLASS-13.0: 27171204
ETIMETIM 9.0: EC001457
UNSPSCUNSPSC 21.0: 39121600
Description
Plug-in lightning and surge arrester combination, in accordance with Type 1+2/Class I+II, for 3-phase power supply networks, with combined PE and N installed in one conductor (L1, L2, L3, PEN).
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01865.pdf

Flyer_00002.pdf

Flyer_00003.pdf

Flyer_00001.pdf

Manufacturer_declaration_00787.pdf

Manufacturer_declaration_02077.pdf

Package_slip_00325.pdf

Technical_drawing_40147.pdf