PHOENIX CONTACT 2905677
PHOENIX CONTACT 2905677
PHOENIX CONTACTNot available

TC-2KS40-AI16-EX-PR-CS - Module carrier

Termination Carrier for redundantly connecting 16 MACX Analog Ex i signal conditioners to analog input cards of the Yokogawa CENTUM VP controller, via two KS40 connectors, 40-pos. Suitable for Yokogawa AAI141 and AAI143 cards.
Product Code: 2905677
Partner cod.: 2905677
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral: For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.
Product propertiesProduct type: Module carrier
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Air clearances and creepage distances
Insulation: Basic insulation
Overvoltage category: II
Pollution degree: 2
Electrical propertiesMax. permissible current: 1 A (Signal/channel)
Nominal voltage UN: < 30 VDC (Per signal/channel)
Air clearances and creepage distances
Rated insulation voltage: 50 V
Rated surge voltage: 0.5 kV
Supported controller YOKOGAWA CENTUM VP
Suitable I/O card: AAI141
AAI143
Supply
Designation: Power module
Note: Power supply via 2904673 TC-MACX-MCR-PTB power supply and error signaling module.
Fuse: 2x 2.5 A on PCB, slow-blow (replaceable)
Input voltage: 24 VDC
Input voltage range: 19.2 VDC ... 30 VDC
Input current: ≤ 2 A
Redundant supply: yes, decoupled from diodes
Polarization and surge protection: Yes
Output name: Switching output
Contact switching type: 1 N/C contact (alarm = open)
Maximum switching voltage: 50 VDC (0.3A)
30 VDC (2A)
33 VAC (2A)
Connection dataPower supply
Connection method: Screw connection
Stripping length: 7 mm
Number of connections: 1
Number of positions: 6
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12
Controller level
Connection method: Yokogawa KS-compatible
Number of connections: 2
Number of positions: 40
SignalingStatus display: 1 x red LED (error)
2x green LEDs (PWR1 and PWR2)
DimensionsWidth: 242 mm
Height: 170 mm
Depth: 159.5 mm
Material specificationsFlammability rating according to UL 94: V0
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP00
Ambient temperature (operation): -20°C ... 60°C (Please observe module specifications)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Shock: 15g, according to IEC˽60068-2-27
Vibration (operation): 2g, according to IEC 60068-2-6
ApprovalsUL, USA/Canada
Identification: UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Standards and regulationsAir clearances and creepage distances
Standards/regulations: DINEN50178
MountingMounting type: DIN rail mounting
Assembly instructions: No end clamp
Mounting position: vertical, horizontal
Technical Specs
ECLASSECLASS-11.0: 27141152
ECLASS-13.0: 27141152
ECLASS-12.0: 27141152
ETIMETIM 9.0: EC002780
UNSPSCUNSPSC 21.0: 39121400
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00005.pdf

Application_note_00200.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Manufacturer_declaration_16070.pdf

Package_slip_02382.pdf

Product_information_00033.pdf

Product_information_00678.pdf

Technical_drawing_40185.pdf