Industrial Automation
Input data | AC operation Input voltage: 230 VAC Input voltage range: 184 VAC ... 264 VAC Voltage type of supply voltage: AC Frequency range (fN): 45 Hz ... 55 Hz 55 Hz ... 65 Hz Current consumption: 3 A (max.) Power factor (cos phi): 0.8 Input fuse: 10 A 400 V gRL Permissible backup fuse: B6 B10 B16 Digital Control (configurable) Designation: Remote Low signal: Connection to SGnd with < 2.7 ké High signal: Open (> 35 ké between Remote and SGnd) Digital Control Low-Active (configurable) Battery-operated start 230VAC low signal: Connection to SGnd with < 2.7 ké Battery-operated start 230VAC high signal: Open (> 200 ké between Bat.-Start and SGnd) |
Output data | Classification according to IEC 62040-3: VFD-SS-311 Efficiency: > 95 % (100%load, with charged energy storage) ~ 81 % (100%load) Nominal output voltage: 230 VAC Form of output voltage: Pure sine Nominal output current (IN): 3 A Bridging time: 60 s UPS connection in parallel: no UPS connection in series: no Apparent power: 750 VA Nominal power: 600 W (Real power) Crest factor: 2.8 Switch-over time: < 10 ms Connection in parallel: no Connection in series: No Mains operation Nominal output voltage: 230 VAC Nominal output current (IN): 3 A (750 VA) Battery operation Nominal output voltage: 230 VAC Nominal output current (IN): 3 A (750 VA) Frequency (after automatic detection in mains operation): 50 Hz 60 Hz Signal: Alarm Output voltage: 24 V (SELV) Continuous load current: ⤠20 mA Signal: Battery mode Output voltage: 24 V (SELV) Continuous load current: ⤠20 mA Signal: Ready Output voltage: 24 V (SELV) Continuous load current: ⤠20 mA Signal: Signal ground SGnd: Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start |
Energy storage | Nominal voltage UN: 24 VDC Charging current: 0.7 A ... 1.1 A Nominal capacity: 4 Ah Nominal capacity range: 4 Ah Charging time: 7 h Buffer period: 20 min. (100 W) 4 min. (300W) 1 min. (600W) Latest startup date (battery only): 6 Months (0°C ... 20°C) Latest startup (battery only) - range: 6 Months ... 3 Months (20°C...30°C) 3 Months ... 1 Months (30°C ... 40°C) Battery technology: Lead rechargeable battery module Memory medium: Lead rechargeable battery module Accumulator type: 2x Panasonic UP-VW1220P1 / BB Battery HR4.2-12FR Can be extended with external battery: 1x 24 V 4 Ah Battery fuse: 40 A, 32 V |
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 10 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Interfaces | Interface: MINI-USB type B Maximum cable length: 3 m |
Signaling | Types of signaling: LED Signal output: Transistor output, active Signalization designation: Alarm Status display: LED Color: red Signal output: Transistor output, activeâ Signalization designation: Battery mode Status display: LED Color: yellow Signal output: Transistor output, activeââ Signalization designation: Ready Signal output Status display: LED Color: green Signal outputâ Signalization designation: Battery charge Status display: LED Color: yellow Signal outputââ Signalization designation: Service Status display: LED Color: red |
Electrical properties | Number of phases: 1.00 |
Product properties | Product type: AC UPS Product family: TRIO AC UPS â UPS with integrated energy storage MTBF (IEC 61709, SN 29500): > 206000 h (40°C) Insulation characteristics Protection class: I Overvoltage category: III Degree of pollution: 2 Life expectancy (electrolytic capacitors) Time: 32000 h |
Dimensions | Width: 210 mm Height: 170 mm Depth: 136 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: DIN rail mounting |
Material specifications | Type of housing: DX51D+AZ (steel sheet / Galvalume) Hood version: PC + ABS |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): 0°C ... 40°C Ambient temperature (storage/transport): -15°C ... 40°C (with charged energy storage device) Maximum altitude: ⤠3000 m (> 2000 m, observe derating) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ⤠95 % (25°C, non-condensing) Shock: 20g in all directions (EN 60068-2-27) 30g in each space direction with UWA 130 Vibration (operation): 5Hz...100Hz, 0.7g (EN60068-2-6) |
Standards and regulations | Standards Standard uninterruptible power supply systems: EN62040-1 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Noise emission in accordance with EN62040-2 Noise immunity: Immunity in accordance with EN62040-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN62040-02 (Class C2) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 3 GHz Test field strength: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 2 kV (Test Level 3 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A (B for USB) Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V Power frequency magnetic field Standards/regulations: EN61000-4-8 Frequency: 50 Hz Test field strength: 100 A/m Comments: Criterion A Emitted interference Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
ECLASS | ECLASS-11.0: 27040705 ECLASS-13.0: 27040705 ECLASS-12.0: 27040705 |
ETIM | ETIM 9.0: EC000382 |