Product properties | IEC test classification: II / III T2 / T3 EN type: T2 / T3 IEC power supply system: TT TN-C IT Type: Installation module Product type: Surge arrester Surge protection fault message: optical Insulation characteristics Protection class: II Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Nominal voltage UN: 100 VAC ... 277 VAC Dielectric strength: < 6 kV |
Connection data | Connection method: Screw terminal blocks Screw thread: M3 Tightening torque: 0.6 Nm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9d19fe157ab7974780e2746e30c4dc4f/-S204x204-FJPG Width: 36.5 mm Height: 56 mm Depth: 34 mm |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6 Material group: I Housing material: PA 6.6 |
Protective circuit | Mode of protection: L-N Direction of action: 1L-N Nominal voltage UN: 100 VAC ... 277 VAC Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 320 VAC Rated load current IL: 16 A Nominal discharge current In (8/20) µs: 5 kA Maximum discharge current Imax (8/20) µs: 10 kA Combination wave UOC: 10 kV Short-circuit current rating ISCCR: 3 kA Voltage protection level Up: ⤠1.3 kV Residual voltage Ures: ⤠1.3 kV (at In) ⤠1.3 kV (at UOC) TOV behavior at UT: 400 VAC (5s / withstand mode) 528 VAC (120min / safe failure mode) Response time tA: ⤠25 ns Max. backup fuse with V-type through wiring: 16 A (MCB B/C) Max. backup fuse with branch wiring: 16 A (MCB B/C) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: 4 mm screw |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 9.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |