Industrial Automation
Product properties | Product type: Limit value switch Product family: MACX Analog Type: Signal conditioners with SIL and PL Functional Safety Configuration: DIP switches Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches |
Electrical properties | Electrical isolation: 3-way isolation Switching point accuracy: < 0.1 % Step response (0â99%): ⤠22 ms Maximum temperature coefficient: 0.01 %/K Maximum transmission error: 0.1 % Electrical isolation Output/supply Rated insulation voltage: 250 VAC (IEC/EN60079-7) Electrical isolation Input/output/power supply Rated insulation voltage: 300 VAC (EN61010-1) Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation in accordance with IEC/EN61010-1 Electrical isolation Input/output, power supply Rated insulation voltage: 375 VAC (IEC/EN60079-7) Supply Nominal supply voltage: 24 VDC Supply voltage range: 9.6 VDC ... 30 VDC (12VDC...24VDC (-20%...+25%)) Typical current consumption: 38 mA (24VDC) Max. current consumption: 90 mA (10VDC) Power dissipation: < 0.9 W Power consumption: ⤠1.2 W |
Input data | Signal: Voltage/current Voltage input signal: 0.1 V ... 10 V 0.1 V ... 10.5 V (Maximum range) Total error of the voltage input maximum: ± 10 mV Current input signal: 0.2 mA ... 20 mA 0.18 mA ... 21 mA (Maximum range) Total error of the current input maximum: ± 20 µA Input resistance of voltage input: > 100 ké Input resistance current input: < 28 é Switching threshold "0" signal current: Configurable via DIP switch (in1.25% increments) and potentiometer (linearly up to 2% of the switching threshold set via the DIP switch) Switching hysteresis: off: approx. 0.5%, on: approx. 1% Line fault detection: < 0.1 mA (Line break) > 21.1 mA (Short circuit) |
Output data | Switching: Relay Contact switching type: 1changeover contact Contact material: AgSnO2, hard gold-plated Max. switching current: ⤠4 A AC (cos phi = 1) ⤠1 ADC (ohmic load, 24VDC, 50mW) ⤠0.2 ADC (ohmic load, 120VDC) |
Connection data | Connection method: Push-in connection Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 14 Test socket Max. diameter: 2 mm |
Ex data | Ex installation (EPL): Gc Div.2 |
Signaling | Status display: Green LED (supply voltage) Yellow LED (switching output) Red LED, flashing (line, sensor error, ERR) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d4485e18fd60154ba93005f91a55c68d/-S204x204-FJPG Width: 12.5 mm Height: 116 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 65°C (Any mounting position) Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant Note: and EN61326 ATEX Identification: ï II 3G Ex ec nC IIC T4 Gc Certificate: TÃV 18 ATEX 8222 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec nC IIC T4 Gc Certificate: PxCIF21UKEX2906169X IECEx Identification: Ex ec nC IIC T4 Gc Certificate: IECEx TUR 18.0014X CCC/China-Ex Identification: Ex ec nC IIC T4 Gc Certificate: 2022122304115959 INMETRO Identification: Ex ec nC IIC T4 Gc Certificate: DNV 21.0089 X UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC T4 Shipbuilding approval Certificate: DNV GL TAA000020C EAC Identification: 2Ex e nC IIC T4 Gc X Certificate: RU C-DE.HB49.B.00145/21 Safety Integrity Level (SIL, IEC 61508) Identification: 2 Certificate: TÃV Rheinland 968/FSP 1481.00/17 Note: Single-channel Safety Integrity Level (SIL, IEC 61508)â Identification: 3 Certificate: TÃV Rheinland 968/FSP 1481.00/17 Note: Two-channel Systematic Capability Identification: 3 Performance Level (ISO13849) Identification: c DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | Electrical isolation: 3-way isolation GBStandard Standards/regulations: GB3836.1 GB3836.3 GB3836.8 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27210120 ECLASS-12.0: 27210120 ECLASS-13.0: 27210120 |
ETIM | ETIM 9.0: EC002653 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products