PHOENIX CONTACT 2906232
PHOENIX CONTACTNot available

PACT RCP-4000A-UIRO-D140 - Current transformer

Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.
The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
Product Code: 2906232
Partner cod.: 2906232
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Current transformer
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesElectrical isolation: Reinforced insulation in accordance with IEC 61010-1
Typical measuring error: < 1 %
Protective circuit: Surge protection; 33V suppressor diode
Step response (0–99%): 110 ms
Rated insulation voltage: 300 V
Measuring coil
Conductor structure signal line: 2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Insulation: double insulation
Rated insulation voltage: 1000 VAC (rms CAT III)
600 VAC (rms CAT IV)
Test voltage: 10.45 kV DC (60 s)
Basic accuracy: <± 0.2 %
Measuring transducers
Maximum transmission error: ≤ 0.5 % (From the range end value)
Frequency range: 16 Hz ... 1000 Hz
Test voltage: 3 kV (50Hz, 1min.)
General
Can be calibrated: no
Class: 1
Accuracy class: 1
Converter type: Rogowski coil and 4-way signal conditioner
Supply: Measuring transducers
Nominal supply voltage: 24 VDC
Nominal supply voltage range: 9.6 VDC ... 30 VDC
Power consumption: ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Input dataFrequency
Designation: Measuring coil
Frequency measuring range: 40 Hz ... 20000 Hz
Position error: <± 0.1 % (typical)
Linearity error: < 0.1 %
Signal
Input signal (at 50 Hz): 100 mV (1000 A)
Curve type: Sine
Input impedance: > 100 kΩ
Current transformers
Configurable/programmable: Via DIP switches
Rated frequency: Standard converter: 40 Hz ... 20000 Hz
Primary rated current Ipn: 0 A AC ... 100 A AC
0 A AC ... 250 A AC
0 A AC ... 400 A AC
0 A AC ... 630 A AC
0 A AC ... 1000 A AC
0 A AC ... 1500 A AC
0 A AC ... 2000 A AC
0 A AC ... 4000 A AC
Can be calibrated: no
Class: 1
Accuracy class: 1
Converter type: Rogowski coil and 4-way signal conditioner
Output dataSwitching: Transistor
Number of outputs: 1
Contact switching type: 1 N/O contact
Minimum switching voltage: 1 V
Maximum switching voltage: 30 VDC
Min. switching current: 100 µA
Max. switching current: 100 mA (at 30 V)
Signal
Designation: Measuring coil
Output signal (at 50 Hz): 100 mV (no load, at 1,000 A)
Output voltage (in no-load operation): VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation): 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
Accuracy class: 1
Signal​
Designation: Measuring transducer
Configurable/programmable: Yes
Voltage output signal: 0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Max. voltage output signal:  12.3 V
Current output signal: 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. current output signal: 24.6 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: ≤ 600 Ω (20mA)
Ripple: < 20 mVPP
Connection dataMeasuring transducer side
Connection method: Screw connection
Stripping length: 10 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 26 ... 16
Tightening torque: 0.5 Nm ... 0.6 Nm
DimensionsItem dimensions
Width: 6.2 mm
Height: 110.5 mm
Depth: 120.5 mm
Measuring coil
Length: 450 mm
Diameter: 8.3 mm ±0.2mm
Measuring coil when installed
Diameter: 140 mm
Signal line
Length: 3 m
Width: 6.2 mm
Height: 110.5 mm
Depth: 120.5 mm
Material specificationsCoil material: Elastollan
Housing material: PC
PBT
Environmental and real-life conditionsAmbient conditions
Measuring coil degree of protection: IP67 (not assessed by UL)
Measuring transducer degree of protection: IP20
Ambient temperature (operation): -30°C ... 80°C (Measuring coil)
-40°C ... 70°C (Measuring transducer)
Ambient temperature (storage/transport): -40°C ... 80°C (Measuring coil)
-40°C ... 85°C (Measuring transducer)
Altitude: < 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
CMIM
Certificate: CMIM-compliant
UL, USA/Canada
Identification: UL 61010 Recognized
Note: Measuring coil
UL, USA/Canada​
Identification: UL 508 Listed
Note: Measuring transducer
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Standards and regulationsElectrical isolation: Reinforced insulation in accordance with IEC 61010-1
Standards/regulations: IEC 61010-1
IEC 61010-2-032
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27210902
ECLASS-13.0: 27210902
ECLASS-12.0: 27210902
ETIMETIM 8.0: EC002048
UNSPSCUNSPSC 21.0: 39121000
Description
Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines. The signal conditioner outputs 8 different standard signals on the output side and has one switching output.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03889.pdf

Manufacturer_declaration_18171.pdf

Package_slip_01709.pdf

Technical_drawing_40249.pdf