Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2906293
PHOENIX CONTACTNot available

VAL-MB-T1/T2 600DC-PV/2+V - Lightning/surge arrester type 1/2

Lightning currentarrester/surge protective devicefor 2-pos. isolated and grounded 600VDC PV systems, for DIN rail mounting, temperature-monitored protective elements, status message on the module.
Product Code: 2906293
Partner cod.: 2906293
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: PV I / II
PV T1 / T2
EN type: T1 / T2
IEC power supply system: DC
Type: DIN rail module, one-piece
Product type: PV arrester
Product family: VALVETRAB MB
Installation location: Interior
Installation location of the disconnect device: Internal
Accessibility: Accessible
Connection configuration: Y configuration
SPD failure behavior: OCFM (Open-Circuit Failure Mode)
Surge protection fault message: optical
Insulation characteristics
Pollution degree: 2
Connection dataConnection method: Screw connection
Screw thread: M5
Tightening torque: 3 Nm
Stripping length: 16 mm
Conductor cross section flexible: 2.5 mm² ... 35 mm²
Conductor cross section AWG: 14 ... 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f287b5e8e540194fb41b84c8d6131892/-S204x204-FJPG
Width: 71.2 mm
Height: 120 mm
Depth: 65.5 mm
Horizontal pitch: 4 Div.
Material specificationsFlammability rating according to UL 94: V-0
Insulating material: PA 6.6
PBT
Housing material: PA 6.6
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: (L+) - (L-)
(L+) - PE
(L-) - PE
Direction of action: (L+)-PE & (L-)-PE & (L+)-(L-)
Rated load current IL: 50 A
Residual current IPE: ≤ 45 µA DC
≤ 420 µA AC
Standby power consumption PC: ≤ 36 mVA
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Impulse discharge current (10/350)µs, charge: 3.125 As
Impulse discharge current (10/350)µs, specific energy: 9.77 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 6.25 kA
Total discharge current Itotal (8/20)µs: 40 kA
Total discharge current Itotal (10/350)µs: 12.5 kA
Voltage protection level Up: ≤ 2.9 kV
Residual voltage Ures: ≤ 2.9 kV (at In)
≤ 2.1 kV (at 3kA)
≤ 2.4 kV (at 6.25 kA)
≤ 2.5 kV (at 10 kA)
≤ 2.8 kV (at 15 kA)
≤ 3.6 kV (at 40 kA)
Response time tA: ≤ 25 ns
PV protective circuit
Connection configuration: Y configuration
SPD failure behavior: OCFM (Open-Circuit Failure Mode)
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC: ≤ 667 VDC
Maximum discharge current Imax (8/20) µs: 40 kA
Response time tA: ≤ 25 ns
Impulse discharge current (10/350)µs, charge: 3.125 As
Impulse discharge current (10/350)µs, specific energy: 9.77 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 6.25 kA
Total discharge current Itotal (8/20)µs: 40 kA
Total discharge current Itotal (10/350)µs: 12.5 kA
Insulation resistance Riso: > 5 GΩ (at 500 V DC)
Nominal discharge current In (8/20) µs: 20 kA
Rated load current IL: 50 A
Continuous operating current ICPV: < 45 µA
Maximum continuous operating voltage UCPV: 800 VDC
Short-circuit current rating ISCPV: 2000 A
Residual voltage Ures: ≤ 2.9 kV (at In)
≤ 2.1 kV (at 3kA)
≤ 2.4 kV (at 6.25 kA)
≤ 2.5 kV (at 10 kA)
≤ 2.8 kV (at 15 kA)
≤ 3.6 kV (at 40 kA)
Residual current IPE: ≤ 45 µA DC
≤ 420 µA AC
Voltage protection level Up: ≤ 2.9 kV
Standby power consumption PC: ≤ 36 mVA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 6000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z)
Standards and regulationsStandards/specifications: EN61643-31
IEC 61643-31
Note: 2019
2018
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171401
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01638.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00844.pdf

Manufacturer_declaration_02095.pdf

Package_slip_00465.pdf

Technical_drawing_40266.pdf