Industrial Automation
PLT-T3-IT-230-FM - Type 3 surge protection device
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Product properties | IEC power supply system: IT Type: Base element, DIN rail mounting Product type: Device protection Number of positions: 2 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Overvoltage category: III Pollution degree: 2 IEC test classification: III T3 EN type: T3 Number of ports: One |
Electrical properties | Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: N/C contact Operating voltage: 250 VAC 125 VDC (200 mA DC) Operating current: 3 A AC 1 ADC (30VDC) |
Connection data | Connection method: Screw connection Screw thread: M3 Tightening torque: 0.8 Nm Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/ccdf98a6bdd749498f6c4126115c9c5f/-S204x204-FJPG Width: 17.7 mm Height: 90 mm Depth: 65.5 mm Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6 Housing material: PA 6.6 |
Protective circuit | Mode of protection: L-L L-PE Direction of action: 1L-N & N-PE Nominal voltage UN: 230VAC(IT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous operating voltage UC (L-L): 275 VAC Maximum continuous operating voltage UC (L-N): 275 VAC Maximum continuous operating voltage UC (L-PE): 440 VAC Rated load current IL: 16 A (60°C) Residual current IPE: ⤠1 µA Standby power consumption PC: ⤠340 mVA Reference test voltage UREF: 255 VAC Nominal discharge current In (8/20) µs: 3 kA Maximum discharge current Imax (8/20) µs: 8 kA Combination wave UOC: 6 kV Voltage protection level Up (L-L): ⤠1.2 kV Voltage protection level Up (L-N): ⤠1.2 kV Voltage protection level Up (L-PE): ⤠1.5 kV Residual voltage at Iamax, (L-PE): ⤠1 kV (at 1 kA) ⤠1.5 kV (at UOC) TOV behavior at UT (L-PE): 440 VAC (120min / withstand mode) 1455 VAC (200ms / safe failure mode) Response time tA (L-N): ⤠25 ns Response time tA (L-PE): ⤠100 ns Max. required back-up fuse: 16 A (MCB B) Short-circuit current rating ISCCR: 1.5 kA AC Max. backup fuse with branch wiring: 16 A (MCB B) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130806 ECLASS-13.0: 27171203 |
ETIM | ETIM 9.0: EC000942 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products