Industrial Automation
REL-OR3/LDP-220DC/3X21 - Single relay
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Product properties | Product type: Single relay Operating mode: 100% operating factor Mechanical service life: 1x 107 cycles, approximately Insulation characteristics Insulation: Basic insulation Insulation characteristicsâ Insulation: Basic insulation Overvoltage category: III Pollution degree: 3 |
Electrical properties | Maximum power dissipation for nominal condition: 1.76 W Test voltage (Winding/contact): 2.5 kVrms (50Hz, 1min., winding/contact) Test voltage (Changeover contact/changeover contact): 2 kVrms (50Hz, 1min., changeover contact/changeover contact) Rated insulation voltage: 250 VAC Rated surge voltage: 4 kV |
Input data | Coil side Nominal input voltage UN: 220 VDC Input voltage range: 187 VDC ... 242 VDC Input voltage range in reference to UN: see diagram Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 8 mA Typical response time: 18 ms Typical release time: 7 ms Protective circuit: Freewheeling diode Status display: Yellow LED |
Output data | Switching Contact switching type: 3 changeover contacts Type of switch contact: Single contact Contact material: AgNi Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 10 V (At 24 mA) Limiting continuous current: 10 A Maximum inrush current: 30 A (20 ms, N/O contacts) Min. switching current: 10 mA (at 24V) Interrupting rating (ohmic load) max.: 240 W (at 24 V DC) 124 W (at 48 V DC) 108 W (at 60 V DC) 52 W (at 110 V DC) 48 W (at 220 V DC) 2500 VA (for 250 V AC) Switching capacity min.: 0.24 W Switching capacity: 2 A (at 24 V, DC13) 1.5 A (at 230 V, AC15) |
Connection data | Connection method: Plug-in connection |
Dimensions | Width: 35 mm Height: 35 mm Depth: 54.4 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: RT I Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | Standards/regulations: IEC 60664 IEC 61810 |
Mounting | Mounting position: any |
ECLASS | ECLASS-11.0: 27371601 ECLASS-12.0: 27371601 ECLASS-13.0: 27371601 |
ETIM | ETIM 9.0: EC001437 |
UNSPSC | UNSPSC 21.0: 39122300 |
Description other products