Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2907042
PHOENIX CONTACTNot available

VAL-MS-T1/T2 48/12.5/2+0/1U/FM - Lightning/surge arrester type 1/2

Universal varistor-based plug-in lightning/surge arrester for 48 V DC applications with grounded return conductor (positive pole), without risk assessment for Lightning Protection Levels III and IV, with remote indication contact.
Product Code: 2907042
Partner cod.: 2907042
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
I
EN type: T1 / T2
IEC power supply system: TN-S
Type: DIN rail module, two-section, divisible
Product type: Arrester combination
Product family: VALVETRAB MS
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 5 VAC ... 250 VAC
125 VAC (UL)
125 VDC (200 mA DC)
Operating current: 5 mA AC ... 1.5 A
1 A (UL)
1 A (30VDC)
Connection dataConnection method: Screw connection
Screw thread: M5
Tightening torque: 2.5 Nm ... 3 Nm
22 lbf-in. ... 26.5 lbf-in. (UL)
Stripping length: 16 mm
Conductor cross section flexible min.: 1.5 mm²
Conductor cross section flexible max.: 25 mm²
Conductor cross section, rigid min.: 1.5 mm²
Conductor cross section, rigid max.: 35 mm²
Conductor cross section flexible: 1.5 mm² ... 25 mm²
Conductor cross section rigid: 1.5 mm² ... 35 mm²
Conductor cross section AWG: 15 ... 2
10 ... 2 (UL)
Remote fault indicator contact
Connection method: Push-in spring connection
Stripping length: 6 mm
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 0.5 mm²
Conductor cross section, rigid min.: 0.14 mm²
Conductor cross section, rigid max.: 0.5 mm²
Conductor cross section flexible: 0.2 mm² ... 0.5 mm²
Conductor cross section rigid: 0.14 mm² ... 0.5 mm²
Conductor cross section AWG: 24 ... 20 (UL)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/1932253809ef1641bc2f9f066d53fc7c/-S204x204-FJPG
Width: 70.6 mm
Height: 40.6 mm
Height unit: 1 U
Depth: 98.1 mm
Horizontal pitch: 4 Div.
Material specificationsFlammability rating according to UL 94: V-0
Housing material: PA 6.6
PBT
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-PE
N-PE
Direction of action: N-PE
L-PE
Nominal voltage UN: 60VAC ±10% (TN-S)
-48 VDC ±10% (RRH)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 75 VAC
100 VDC
Rated load current IL: 80 A
Residual current IPE: ≤ 0.6 mA
Standby power consumption PC: ≤ 45 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 30 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Total discharge current Itotal (8/20)µs: 50 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 0.4 kV
Residual voltage Ures: ≤ 0.4 kV (at In)
≤ 0.35 kV (at 10 kA)
≤ 0.3 kV (at 5 kA)
≤ 0.275 kV (at 4 kA)
≤ 0.25 kV (at 3kA)
TOV behavior at UT: 100 VAC (5s / withstand mode)
130 VDC (5s / withstand mode)
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 80 A AC (gG - 16 mm²)
Max. backup fuse with branch wiring: 160 A AC (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 65 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV (L-N): 75 VAC
100 VDC
Mode of protection: L-G
(L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage: 60 VDC
SPD Type: 1CA
UL indicator/remote signaling
Operating voltage: 125 VAC
AC operating current: 1 A AC
UL connection data
Tightening torque: 30 lbf-in.
Conductor cross section AWG: 10 ... 2
MountingMounting type: Panel mount
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Description
Universal varistor-based plug-in lightning/surge arrester for 48 V DC applications with grounded return conductor (positive pole), without risk assessment for Lightning Protection Levels III and IV, with remote indication contact.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01874.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00079.pdf

Manufacturer_declaration_02907.pdf

Manufacturer_declaration_16220.pdf

Package_slip_00068.pdf

Technical_drawing_40417.pdf