QUINT4-UPS/24DC/24DC/10/PN - Uninterruptible power supply

QUINT UPS with IQ Technology, RJ45 communication interfaces (PROFINET), for DIN rail mounting, input: 24 V DC, output: 24 V DC / 10 A, charging current: 3 A
Product Code: 2907068
Partner cod.: 2907068
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataInput voltage: 24 VDC
Input voltage range: 18 VDC ... 30 VDC
18 VDC ... 32 VDC
Internal input fuse: no
Voltage type of supply voltage: DC
Inrush current: ≤ 7 A (≤4ms)
Reverse polarity protection: yes
Fixed backup threshold: 22 VDC
30 VDC
Dynamic activation threshold: > 1V / 100ms
Switch-on time: max. 3 s
Switch-on time during battery operation (Bat.-Start): 8 s
Voltage drop, input/output: 0.4 VDC
Current consumption IN (UN, IOUT = IN, Icharge = 0): 10.1 A
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max): 16.3 A
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0): 105 mA
Current consumption Icharge (UN, IOUT = 0, Icharge = max): 3.7 A
Power consumption PN (UN, IOUT = IN, Icharge = 0): 245 W
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max): 386 W
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0): 2.6 W
Power consumption Pcharge (UN, IOUT = 0, Icharge = max): 92 W
Output dataEfficiency: typ. 97 %
Number of outputs: 1
Short-circuit-proof: yes
No-load proof: yes
Switch-over time: 0 ms
UPS connection in parallel: no
UPS connection in series: no
Energy storage device connection in parallel: Yes, 5 (observe line protection)
Energy storage device connection in series: no
Mains operation
Output voltage: 24 VDC (UOUT = UIN - 0.4VDC)
Output voltage range: 18 VDC ... 30 VDC
18 VDC ... 32 VDC
Output current IN: 10 A
Static Boost (IStat.Boost): 12.5 A
Dynamic Boost (IDyn.Boost): 20 A (5 s)
Selective Fuse Breaking (ISFB): 60 A (15 ms)
Output power POUT (UN, IOUT = IN): 240 W
Output power POUT (UN, IOUT = Istat.Boost): 300 W
Output power POUT (UN, IOUT = Idyn.Boost): 480 W (5 s)
Power dissipation No load (UN, IOut = 0, ICharge = 0): 1 W
Power dissipation Nominal load (UN, IOut = IN, ICharge = 0): 6 W
Battery operation
Output voltage: 24 VDC (UOUT = UBAT - 0.4VDC)
Output voltage range: 19 VDC ... 32 VDC
Output current IN: 10 A
Static Boost (IStat.Boost): 12.5 A
Dynamic Boost (IDyn.Boost): 20 A (5 s)
Selective Fuse Breaking (ISFB): 60 A (15 ms)
Output power POUT (UN, IOUT = IN): 240 W
Output power POUT (UN, IOUT = Istat.Boost): 300 W
Output power POUT (UN, IOUT = Idyn.Boost): 480 W (5 s)
Energy storageEnd-of-charge voltage: 32 VDC
End-of-charge voltage (temperature-compensated): 25 VDC ... 32 VDC
Charging current (configurable): 3 A
Nominal capacity (without additional charger): 1.2 Ah ... 60 Ah
Max. capacity: 80 Ah
Charging time: 120 h
Buffer time: 25 min. (7.2 Ah)
Deep discharge protection: 19.2 VDC
Battery technology: VRLA, VRLA-WTR, LI-ION
Charge characteristic curve: IU0U
IQ-Technology: yes
Temperature sensor: yes
Temperature compensation (configurable): 42 mV/K
InterfacesInterface: PROFINET
Number of interfaces: 2
Connection method: RJ45
Locking: Locking clip
Transmission physics: Twisted-Pair
Features: Autonegotiation
Autocrossing
Autopolarity
full duplex
Topology: Star
Line
Transmission speed: 100 Mbps
Transmission length: max. 100 m
Cycle time: 1 ms (RT)
Access time: ≤ 2 s
Standards: IEEE 802.3
IEC 61158
IEC 61784-2
Supported protocols: PROFINET
LLPD
Chipset: Renesas TPS-1
Electrical isolation: yes
Device ID: 0142hex
Vendor ID: 00B0hex
SignalingLED signaling
Types of signaling: DC OK (green)
Alarm (red)
Bat.-Mode (yellow)
SOC (red, green)
Data (red, green)
Product propertiesProduct type: DC UPS
Product family: QUINTUSV
MTBF (IEC 61709, SN 29500): > 1189000 h (25°C)
> 736900 h (40°C)
> 372700 h (60°C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: III (without PE)
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Time: 137895 h
DimensionsItem dimensions
Width: 35 mm
Height: 130 mm
Depth: 125 mm
125 mm (Device depth (DIN rail mounting))
Item dimensions with alternative mounting
Width: 123 mm
Height: 130 mm
Depth: 37 mm
Installation dimensions
Installation distance right/left (active): 5 mm / 5 mm (POut≥50%)
Installation distance right/left (passive): 0 mm / 0 mm (POut≥50%)
Installation distance right/left (active, passive): 0 mm / 0 mm (POut≤50%)
Installation distance top/bottom (active): 50 mm / 50 mm (POut≥50%)
Installation distance top/bottom (passive): 40 mm / 20 mm (POut≥50%)
Installation distance top/bottom (active, passive): 40 mm / 20 mm (POut≤50%)
MountingMounting type: DIN rail mounting
Mounting position: On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum AlMg3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 4000 m
Climatic class: 3K3 (EN60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 2.3g
Standards and regulationsOvervoltage category
EN 61010-1: II(≤4000m)
EN61010-2-201: II(≤4000m)
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
ApprovalsUL approval
Identification: UL/C-UL Listed UL61010-1
UL approval​
Identification: UL/C-UL Listed UL61010-2-201
UL approval​​
Identification: UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification: CAN/CSA-C22.2 No.61010-1-12
CSA​
Identification: CAN/CSA-IEC 61010-2-201
CSA​​
Identification: CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CB scheme
Identification: IEC 61010-1
IEC 61010-2-201
DNV
Identification: Class Guideline DNVGL-CG-0339
Note: Location classes: TemperatureD (see Application/Limitation), HumidityB, VibrationA/C, EMCB
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial), and EN61000-6-5 (power station equipment zone), IEC/EN61850-3 (power supply)
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion B
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 16.67 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Technical Specs
ECLASSECLASS-11.0: 27040705
ECLASS-12.0: 27040705
ECLASS-13.0: 27040705
ETIMETIM 9.0: EC000382
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00110.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00951.pdf

Approvals_00952.pdf

Approvals_00953.pdf

Approvals_00963.pdf

Approvals_01337.pdf

Approvals_01501.pdf

Approvals_01529.pdf

Approvals_01625.pdf

Data_sheet_03897.pdf

Manufacturer_declaration_03117.pdf

Manufacturer_declaration_04831.pdf

Manufacturer_declaration_05510.pdf

Manufacturer_declaration_16226.pdf

Package_slip_02161.pdf

Technical_drawing_40426.pdf

Various_00027.pdf

Various_00006.pdf