Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2907263
PHOENIX CONTACTNot available

FLT-SEC-P-T1-N/PE-440/100-P - Type 1 surge protection plug

Replacement plug for lightning current arresters from the FLASHTRAB SEC product range, for the N-PE path.
Product Code: 2907263
Partner cod.: 2907263
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN
TT
Type: Male
Product type: Replacement plug
Product family: SEC Family
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/1a58f52621b8da488117a8b18f8d2431/-S204x204-FJPG
Width: 35.5 mm
Height: 46.4 mm
Depth: 59.4 mm
Horizontal pitch: 2 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: N-PE
Direction of action: N-PE
Nominal voltage UN: 400VAC (TN - only N-PE)
400VAC (TT - only N-PE)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 440 VAC
Residual current IPE: ≤ 0.01 mA
Nominal discharge current In (8/20) µs: 100 kA
Impulse discharge current (10/350)µs, charge: 50 As
Impulse discharge current (10/350)µs, specific energy: 2500 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 100 kA
Follow current interrupt rating Ifi: 100 A (440 V AC)
Voltage protection level Up: ≤ 2.5 kV
Residual voltage Ures: ≤ 2.5 kV (at In)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 2.5 kV
TOV behavior at UT: 1200 VAC (200ms / withstand mode)
Response time tA: ≤ 100 ns
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 440 VAC
Voltage protection rating VPR: 1500 V
Nominal discharge current In: 20 kA
Mode of protection: N-G
Nominal frequency: 50/60 Hz
SPD Type: 1CA
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Description
Replacement plug for lightning current arresters from the FLASHTRAB SEC product range, for the N-PE path.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01864.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Flyer_00003.pdf

Manufacturer_declaration_00788.pdf

Manufacturer_declaration_02049.pdf

Manufacturer_declaration_16245.pdf

Package_slip_00318.pdf

Technical_drawing_40462.pdf