Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2907391
PHOENIX CONTACT 2907391
PHOENIX CONTACTNot available

FLT-SEC-P-T1-264/50-P - Type 1 surge protection plug

Replacement plug for lightning current arresters from the FLASHTRAB SEC PLUS 264 product range, for L-N and L-PEN paths.
Product Code: 2907391
Partner cod.: 2907391
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN
TT
Type: Male
Product type: Replacement plug
Product family: SEC Family
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/1a58f52621b8da488117a8b18f8d2431/-S204x204-FJPG
Width: 35.5 mm
Height: 46.6 mm
Depth: 59.4 mm
Horizontal pitch: 2 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: L-N
L-PEN
Direction of action: L-N / L-PEN
Nominal voltage UN: 240VAC (TN)
240VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 264 VAC
Nominal discharge current In (8/20) µs: 50 kA
Maximum discharge current Imax (8/20) µs: 100 kA
Impulse discharge current (10/350)µs, charge: 25 As
Impulse discharge current (10/350)µs, specific energy: 625 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 50 kA
Follow current interrupt rating Ifi: 50 kA
Short-circuit current rating ISCCR: 50 kA
Voltage protection level Up: ≤ 2.5 kV
Residual voltage Ures: ≤ 2.5 kV (at In)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 2.5 kV
TOV behavior at UT: 415 VAC (5s / withstand mode)
760 VAC (120min / withstand mode)
Response time tA: ≤ 100 ns
Max. backup fuse with branch wiring: 500 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 264 VAC
Short-circuit current rating (SCCR): 50 kA
Voltage protection rating VPR: 1500 V
Nominal discharge current In: 20 kA
Mode of protection: L-N
L-G
Nominal voltage: 240VAC
Power distribution system: Single phase
Nominal frequency: 50/60 Hz
SPD Type: 1CA
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01864.pdf

Flyer_00001.pdf

Flyer_00003.pdf

Flyer_00002.pdf

Manufacturer_declaration_00788.pdf

Manufacturer_declaration_02049.pdf

Package_slip_00304.pdf

Technical_drawing_40475.pdf