PHOENIX CONTACT 2907865
PHOENIX CONTACT 2907865
PHOENIX CONTACTNot available

VAL-SEC-T2-2+0-48DC-FM - Type 2 surge arrester

Pluggable surge protective device, in accordance with Type 2/Class II, for DC power sources with linear operating characteristics, with remote indication contact.
Product Code: 2907865
Partner cod.: 2907865
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: DC
Type: DIN rail module, two-section, divisible
Product type: Surge arrester
Product family: SEC Family
Number of positions: 2
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Nominal voltage UN: 48 VDC ... 60 VDC
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 5 VAC ... 250 VAC (Altitude ≤ 2000 m amsl)
5 VAC ... 150 VAC (Altitude > 2000 m amsl)
125 VDC (200 mA DC)
Operating current: 5 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 16 mm
Conductor cross section flexible: 2.5 mm² ... 16 mm²
1.5 mm² ... 6 mm²
Conductor cross section rigid: 2.5 mm² ... 25 mm²
Conductor cross section AWG: 12 ... 4
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/ca716f833cb13c4a9fc33a7788d5d52c/-S204x204-FJPG
Width: 25.4 mm
Height: 97.9 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 1.4 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: (DC+) - (DC-)
(DC+) - PE
(DC-) - PE
Direction of action: (DC+/DC-) - PE
Nominal voltage UN: 60VAC (TN)
48 VDC ... 60 VDC
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 75 VDC
75 VAC
Rated load current IL: 40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE: ≤ 50 µA DC
≤ 450 µA AC
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Impulse discharge current (10/350)µs, charge: 2 As
Impulse discharge current (10/350)µs, specific energy: 4 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 4 kA
Total discharge current Itotal (8/20)µs: 40 kA
Short-circuit current rating ISCCR: 0.2 kA DC (without backup fuse)
6 kA DC (for 20 A gG/B backup fuse)
10 kA AC (C63A miniature circuit breaker)
25 kA AC (for a backup fuse of up to 315AgG)
50 kA AC (for a backup fuse of up to 200AgG)
Voltage protection level Up (DC+) - (DC-): ≤ 0.9 kV
Voltage protection level Up (DC+/DC-) - PE: ≤ 0.5 kV
Response time tA: ≤ 25 ns
Max. backup fuse with V-type through wiring: 20 ADC (gG / B at ISCCR > 200 A)
Max. backup fuse with branch wiring: 20 ADC (gG / B at ISCCR > 200 A)
315 A AC (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 6000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Short-circuit current rating (SCCR): 50 kA
Voltage protection rating VPR (DC+) - (DC-): 800 V
Voltage protection rating VPR (DC+) - G: 400 V
Voltage protection rating VPR (DC-) - G: 400 V
Nominal discharge current In: 20 kA
Mode of protection: (DC+) - (DC-)
(DC+) - G
(DC-) - G
Nominal voltage: 60 VDC
Power distribution system: DC
SPD Type: 1
UL indicator/remote signaling
Operating voltage: 125 VAC
AC operating current: 1 A AC
UL connection data
Tightening torque: 30 lbf-in.
Conductor cross section AWG: 10 ... 2
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27130805
ECLASS-13.0: 27171302
ETIMETIM 9.0: EC000941
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_00390.pdf

Approvals_01875.pdf

Flyer_00001.pdf

Flyer_00003.pdf

Flyer_00002.pdf

Manufacturer_declaration_00922.pdf

Manufacturer_declaration_02053.pdf

Package_slip_00549.pdf

Technical_drawing_40532.pdf