Notes | General Note: Burst test up to 4kV passed according to DINEN61000-4-4. Insulates against repetitive pulses up to 1.5kV. Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442/ VDE 0100-442 Fig. 44D/ Examplea). At altitudes > 2000 m (amsl), a lateral distance of 2 mm must be maintained between live and grounded parts. |
Product properties | IEC test classification: II T2 EN type: T2 IEC power supply system: IT Type: DIN rail module, two-section, divisible Product type: Surge arrester Product family: VALVETRAB MS Number of positions: 4 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 5 VAC ... 250 VAC (Altitude ⤠2000 m amsl) 5 VAC ... 150 VAC (Altitude > 2000 m amsl) 30 VDC Operating current: 5 mA AC ... 750 mA AC 1 ADC |
Connection data | Connection method: Screw connection Fork-type cable lug Screw thread: M5 Tightening torque: 3 Nm (1.5mm² ... 16mm²) 4.5 Nm (25mm²...35mm²) Stripping length: 16 mm Conductor cross section flexible: 1.5 mm² ... 25 mm² 1.5 mm² ... 16 mm² Conductor cross section rigid: 1.5 mm² ... 35 mm² Conductor cross section AWG: 15 ... 2 Remote fault indicator contact Connection method: Plug-in/screw connection via COMBICON Screw thread: M2 Tightening torque: 0.25 Nm Stripping length: 7 mm Conductor cross section flexible: 0.14 mm² ... 1.5 mm² Conductor cross section rigid: 0.14 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/52a1de3230b149449b5816762603cd12/-S204x204-FJPG Width: 71 mm Height: 98.7 mm Depth: 65.7 mm (incl. DIN rail 7.5mm) Horizontal pitch: 4 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6/PBT Material group: I Housing material: PA 6.6 PBT |
Protective circuit | Mode of protection: L-PE L-L Direction of action: 3L-N/PE Nominal voltage UN: 400VAC (IT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 440 VAC Rated load current IL: 80 A Residual current IPE: ⤠5 µA Standby power consumption PC: ⤠600 mVA Nominal discharge current In (8/20) µs: 20 kA Maximum discharge current Imax (8/20) µs: 40 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up (L-L): ⤠4 kV Voltage protection level Up (L-PE): ⤠3.5 kV Residual voltage Ures (L-L): ⤠4 kV (at In) Residual voltage Ures (L-PE): ⤠2.3 kV (at In) Response time tA (L-L): ⤠25 ns Response time tA (L-PE): ⤠100 ns Max. backup fuse with V-type through wiring: 80 A (gG) Max. backup fuse with branch wiring: 100 A (gG) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠5000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Standards and regulations | Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 9.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |