QUINT4-PS/48DC/24DC/5/PT - DC/DC converter

Primary-switched DC/DC converter, QUINT POWER, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 48 VDC, output: 24 VDC / 5 A
Product Code: 2910125
Partner cod.: 2910125
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Input dataNominal input voltage range: 48 VDC
Input voltage range: 48 VDC -40% ... +20%
Wide-range input: no
Electric strength, max.: 60 VDC (60 s)
Inrush current: typ. 2.5 A
Inrush current integral (I2t): < 0.2 A2s
Inrush current limitation: 2.5 A
Mains buffering time: typ. 18 ms (48VDC)
Current consumption: 3.3 A (48VDC)
Typical response time: 300 ms (from SLEEP MODE)
Switch-on time: < 1 s
Input fuse: 10 A (slow-blow, internal)
Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Signal Remote (configurable)
Connection labeling: 3.3 +
Function: Output power ON/OFF (remote)
Default: Output power ON (>40kΩ/24VDC/open bridge between REM and SGnd)
Output dataEfficiency: typ. 94 % (48VDC)
Output characteristic: U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage: 24 VDC
Setting range of the output voltage (USet): 24 VDC ... 29.5 VDC (> 24VDC, constant capacity)
Nominal output current (IN): 5 A
Static Boost (IStat.Boost): 6.25 A
Dynamic Boost (IDyn.Boost): 10 A (5 s)
Selective Fuse Breaking (ISFB): 30 A (15 ms)
Magnetic circuit breaker tripping: A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
Short-circuit-proof: yes
No-load proof: yes
Output power (PN): 120 W
Output power (PStat. Boost): 150 W
Output power (PDyn. Boost): 240 W (5 s)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): ≤ 32 VDC
Residual ripple: < 15 mVPP
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
Rise time: < 100 ms (UOUT (10 % ... 90 %))
Connection in series: yes
Maximum no-load power dissipation: < 2 W
Power loss nominal load max.: < 8 W
Power dissipation SLEEP MODE: < 1 W
Connection in parallel: yes, for redundancy and increased capacity
Signal Out 1 (configurable)
Connection labeling: 3.5 +
Digital: 0 VDC
24 VDC
20 mA
Signal option: Output voltage
Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Default: UIN input voltage OK
Signal Out 2 (configurable)
Connection labeling: 3.6 +
Digital: 0 VDC
24 VDC
20 mA
Default: Output power
Signal option: Output voltage
Output current
Operating hours
Early warning of high temperatures
OVP voltage limitation active
Output voltage
Output current
Output power
Analog: 4 mA ... 20 mA ±5% (Load ≤400Ω)
Signal relay 13/14 (configurable)
Connection labeling: 3.1, 3.2
Switch contact (floating): floating
Maximum contact load: 24 VDC
1 A
30 VAC
0.5 A
Default: Output voltage
Signal option: Output current
Output power
Operating hours
Early warning of high temperatures
OVP voltage limitation active
UIN input voltage OK
Signal ground SGnd
Connection labeling: 3.4 +
Function: Signal ground
Reference potential: to OUT1, OUT2, REM
Connection dataInput
Position: 1.x
Conductor connection
Connection method: Push-in connection
rigid: 0.2 mm² ... 6 mm²
flexible: 0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve: 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.2 mm² ... 4 mm²
rigid (AWG): 24 ... 10
Stripping length: 10 mm
Output
Position: 2.x
Conductor connection​
Connection method: Push-in connection
rigid: 0.2 mm² ... 6 mm²
flexible: 0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve: 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.2 mm² ... 4 mm²
rigid (AWG): 24 ... 10
Stripping length: 10 mm
Signal
Position: 3.x
Conductor connection​​
Connection method: Push-in connection
rigid: 0.2 mm² ... 1 mm²
flexible: 0.2 mm² ... 1.5 mm²
flexible with ferrule without plastic sleeve: 0.2 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve: 0.2 mm² ... 0.75 mm²
rigid (AWG): 24 ... 16
Stripping length: 8 mm
SignalingLED signaling
Types of signaling: LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal threshold: > 100% (LED lights up yellow, output power > 240W)
> 75% (LED lights up green, output power > 180W)
> 50% (LED lights up green, output power > 120W)
> 0.9xUSet (LED lights up green)
< 0.9xUSet (LED flashes green)
> 0.8 x UInNom (LED off)
< 0.8 x UInNom (LED lights up yellow)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV DC (type test)
2 kV DC (routine test)
Switching frequency: 190 kHz ... 220 kHz (Auxiliary converter stage)
50 kHz ... 420 kHz (Main converter stage)
Product propertiesProduct type: DC/DC converters
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > (25°C)
> 1000000 h (40°C)
> (60°C)
Insulation characteristics
Protection class: Special with SELV input and output
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 2.5 A
Temperature: 40°C
Time: 520000 h
Additional text: 24VDC
Life expectancy (electrolytic capacitors)​
Current: 5 A
Temperature: 40°C
Time: 290000 h
Additional text: 24VDC
Life expectancy (electrolytic capacitors)​​
Current: 5 A
Temperature: 30°C
Time: 590000 h
Additional text: 24VDC
DimensionsItem dimensions
Width: 36 mm
Height: 130 mm
Depth: 125 mm
Item dimensions with alternative mounting
Width: 122 mm
Height: 130 mm
Depth: 39 mm
Installation dimensions
Installation distance right/left (active): 15 mm / 15 mm
Installation distance right/left (passive): 0 mm / 0 mm
Installation distance top/bottom (active): 50 mm / 50 mm
Installation distance top/bottom (passive): 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: PN ≥50%, 5mm horizontally, 15mm next to active components, 50mm vertically
alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K22 (in accordance with EN60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5Hz ... 100Hz resonance search 2.3g, 90min., resonance frequency 2.3g, 90min. (according to DNV GL Class C)
Standards and regulationsOvervoltage category
EN 61010-1: II(≤5000m)
EN 62477-1: III(≤2000m)
Safety for measurement, control, and laboratory equipment
Standard designation: Electrical safety (of control and regulation devices)
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: EN61010-1 (SELV)
IEC 61010-2-201 (PELV)
Mains voltage dips
Standard designation: Mains variation/undervoltage
Standards/specifications: EN61000-4-29
Railway applications
Standard designation: Railway applications
Standards/specifications: EN50121-3-2
IEC 62236-3-2
ApprovalsUL
Identification: ULListedUL61010-1
UL​
Identification: ULListedUL61010-2-201
UL​​
Identification: UL121201 & CSAC22.2No.213-17Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification: CAN/CSA-C22.2 No.61010-1-12
CSA​
Identification: CAN/CSAC22.2No.61010-2-201:18
SIQ
Identification: Type tested (type approved)
SIQ​
Identification: CB scheme (IEC 61010-1, IEC 61010-2-201)
Shipbuilding
Identification: DNV
Shipbuilding​
Identification: ABS
Shipbuilding​​
Identification: BV
Shipbuilding​​​
Identification: NK
Shipbuilding​​​​
Identification: LR
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: IEC 61850-3
EN61000-6-5
Conducted noise emission: EN55016
EN61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
EN55016
EN61000-6-3 (Class B)
DNVGL conducted interference: ClassB
Additional text: Bridge and deck area
DNVGL noise radiation: ClassB
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 2 kV (Test Level 3 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 16.7 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: EN61000-4-29
Voltage: 24 VDC
Voltage dip: 70 %
40 %
0 %
Time: 100 ms
50 ms
Additional text: Test Level 2
Comments: Criterion A
Criterion B
Pulse-shape magnetic field
Standards/regulations: EN61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: EN61000-4-16
Test level 1: 15 Hz 150 Hz (Test Level 3)
Voltage: 10 V 1 V
1 V
1 V 10 V
10 V
10 V (Permanent)
100 V (1 s)
Test level 2: 150 Hz 1.5 kHz (Test Level 3)
Test level 3: 1.5 kHz 15 kHz (Test Level 3)
Test level 4: 15 kHz 150 kHz (Test Level 3)
Test level 5: 16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Test level 6: 0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
Comments: Criterion A
Alternating component of direct voltage
Standards/regulations: EN61000-4-17
Alternating component: 15 % (UN)
14 % (UN)
Frequency: 50 Hz
100 Hz
150 Hz
300 Hz
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: EN61000-4-18
Input, output (test level1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage: 1 kV
0.5 kV
0.5 kV
1 kV
Input, output (test level2): 100 kHz 1 MHz (Test Level 2 - asymmetrical)
Input, output (test level3): 10 MHz (Test Level 2 - asymmetrical)
Signals (test level1): 100 kHz 1 MHz (Test Level 2 - symmetrical)
Signals (test level2): 100 kHz 1 MHz (Test Level 2 - asymmetrical)
Comments: Criterion A
Attenuated oscillating magnetic field
Standards/regulations: EN61000-4-10
Test field strength: 100 A/m
Test level 1: 100 kHz
Test level 2: 1 MHz
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Description
Primary-switched DC/DC converter, QUINT, DIN rail mounting, SFB Technology (Selective Fuse Breaking), Push-in connection, input: 48 V DC, output: 24 V DC / 5 A
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00825.pdf

Approvals_01297.pdf

Approvals_01330.pdf

Approvals_01378.pdf

Approvals_01508.pdf

Data_sheet_03937.pdf

Manufacturer_declaration_03146.pdf

Manufacturer_declaration_04868.pdf

Manufacturer_declaration_05492.pdf

Manufacturer_declaration_16497.pdf

Package_slip_02154.pdf

Technical_drawing_40896.pdf

Various_00006.pdf