Industrial Automation
Notes | General: Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
Product properties | Product type: Solid-state relay module Product family: DEK Application: Inverter module Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 4.8 W Supply Supply voltage range: 20 VDC ... 30 VDC |
Input data | Typical input current at UN: 200 mA Transmission frequency: 15 kHz NPN Switching threshold "1" signal voltage: < 5 V (at UV = 24 V; < (UV - 19 V)) Switching threshold "0" signal, voltage: > 15 V (at UV = 24 V; > (UV - 9 V)) Min. voltage input signal: -2 V Max. voltage input signal: 26 V (at UV = 24 V; UV + 2 V) PNP Switching threshold "1" signal voltage: > 19 V Switching threshold "0" signal, voltage: < 9 V Min. voltage input signal: -2 V Max. voltage input signal: 26 V (at UV = 24 V; UV + 2 V) |
Output data | Continuous load current: 200 mA Leakage current: < 1 mA Residual voltage: < 1 V Transmission frequency: 15 kHz Contact switching type: 1 N/O contact Output nominal voltage: max. ± 26 V |
Connection data | Connection method: Screw connection Stripping length: 8 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 |
Dimensions | Width: 6.2 mm Height: 80 mm Depth: 56 mm |
Material specifications | Housing material: Polyamide PA non-reinforced |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -20°C ... 50°C Ambient temperature (storage/transport): -20°C ... 70°C |
Standards and regulations | Standards/regulations: IEC 60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371604 ECLASS-12.0: 27371604 ECLASS-13.0: 27371604 |
ETIM | ETIM 9.0: EC001504 |
UNSPSC | UNSPSC 21.0: 39122300 |
Description other products