Industrial Automation
Product properties | Product type: Safety relays Product family: PSRclassic Application: Emergency stop Safety door Light grid Mechanical service life: approx. 107 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3 Times Typical response time: 125 ms (automatic start) 110 ms (manual, monitored start) Typ. starting time with Us: 125 ms (when controlled via A1) Typical release time: 10 ms (on demand via the sensor circuit) 45 ms (on demand via A1) Restart time: < 1 s (Boot time) Recovery time: 1 s (following demand of the safety function) |
Electrical properties | Maximum power dissipation for nominal condition: 16.44 W (at US=26.4V, IL²=72A²) Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 V Rated surge voltage/insulation: See section âInsulation coordinationâ Supply Rated control circuit supply voltage US: 24 VDC -15% / +10% Rated control supply current IS: typ. 70 mA (at US) Power consumption at US: typ. 1.68 W Inrush current: < 3.5 A (typically with US, Ãt=3ms) Filter time: 5 ms (in the event of voltage dips at Us) Protective circuit: Serial protection against polarity reversal; Suppressor diode |
Input data | Digital: Logic (S12, S22) Description of the input: safety-related Number of inputs: 2 Input voltage range "0" signal: 0 VDC ... 5 VDC Input voltage range "1" signal: 20.4 V ... 26.4 V Input current range "0" signal: 0 mA ... 2 mA Inrush current: max. 110 mA (typically with US, Ãt=3ms) Filter time: max. 2 ms (Test pulse width low test pulses, at 100ms test pulse rate) No brightness test pulses / high test pulses permitted. Concurrence: â Max. permissible overall conductor resistance: 50 é Protective circuit: Suppressor diode Current consumption: 38 mA (typically with US at S12/S22) Digital: Start circuit (S34, S35) Description of the input: non-safety-related Number of inputs: 2 Input voltage range "1" signal: 20.4 V ... 26.4 V Inrush current: < 6 mA (typically with US at S34/35, Ãt=70ms) Filter time: No test pulses permitted Max. permissible overall conductor resistance: 50 é Protective circuit: Suppressor diode Current consumption: 0 mA (Typically with US at S34) 1 mA (Typically with US at S35) |
Output data | Relay: Enabling current paths (13/14, 23/24, 33/34) Output description: 2 N/O contacts each in series, safety-related, floating Number of outputs: 3 Contact switching type: 3 enabling current paths Contact material: AgSnO2 Switching voltage: min. 10 V max. 250 VAC Switching capacity: min. 100 mW Inrush current: min. 10 mA max. 6 A Switching capacity in accordance with IEC 60947-5-1: max. 5 A (AC15) max. 6 A (DC13) Limiting continuous current: max. 6 A (Observe derating and load limit curve) Sq. Total current: max. 72 A2 (observe derating) Switching frequency: max. 0.5 Hz Mechanical service life: 10x 106 cycles Output fuse: 10 A gL/gG 4 A gL/gG (for low-demand applications) Relay: Signaling current path (41/42) Output description: 2 N/C contacts parallel, non-safety-related, floating Contact switching type: 2NC parallel Contact material: AgSnO2 Switching voltage: min. 10 V AC/DC max. 250 VAC Switching capacity: min. 100 mW Inrush current: min. 10 mA max. 6 A Switching capacity in accordance with IEC 60947-5-1: 1.5 A (AC15) 2 A (DC13) Limiting continuous current: 6 A Sq. Total current: 36 A2 Switching frequency: max. 0.5 Hz Mechanical service life: 10x 106 cycles Output fuse: 6 A gL/gG |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm |
Signaling | Status display: 2 x green LEDs Operating voltage display: 1 x green LED |
Dimensions | Width: 22.5 mm Height: 117.5 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENISO13849 Category: 4 Performance level (PL): e Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 3 Safety data: ENIEC 62061 Safety Integrity Level (SIL): 3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C (observe derating) Ambient temperature (storage/transport): -40°C ... 70°C Maximum altitude: ⤠2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10Hz...150Hz, 2g |
Approvals | CE Identification: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINEN60947-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: See derating curve Mounting position: vertical or horizontal Connection method: Push-in connection |
ECLASS | ECLASS-11.0: 27371819 ECLASS-13.0: 27371819 ECLASS-12.0: 27371819 |
ETIM | ETIM 9.0: EC001449 |
UNSPSC | UNSPSC 21.0: 39122200 |