Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2981363
PHOENIX CONTACTAvailable

PSR-SCF- 24UC/URM/2X21 - Coupling relay

Safe coupling relay with force-guided contacts, 2 changeover contacts, 1-channel, fixed screw terminal block, width: 17.5mm
Product Code: 2981363
Partner cod.: 2981363
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Coupling relay
Product family: PSRclassic
Application: Safe switch off
High demand
Low demand
Mechanical service life: 10x 106 cycles
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Times
Restart time: < 1 s (Boot time)
Recovery time: < 500 ms
Electrical propertiesMaximum power dissipation for nominal condition: 5.87 W (at UB=26.4VDC, US=24V, IS=30mA, n=1, IL²=50A², Rcontact=0.1)
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 V
Rated surge voltage/insulation: 4 kV/basic insulation (safe isolation, reinforced insulation, and 6 kV between logic and signaling current paths).
Input dataGeneral
Rated control circuit supply voltage US: 24 V AC/DC -15% / +10%
Power consumption at US: typ. 0.72 W
Rated control supply current IS: typ. 30 mA
Input voltage range: 20.4 V AC/DC ... 26.4 V AC/DC
Typ. starting time with Us: typ. 10 ms
Typical release time: typ. 10 ms
Recovery time: < 500 ms
Maximum switching frequency: 0.5 Hz
Operating voltage display: 1 x yellow LED
Output dataContact switching type: 2 changeover contacts
Contact material: AgNi
Maximum switching voltage: 230 V AC/DC (Observe the load curve)
Minimum switching voltage: 5 V AC/DC
Limiting continuous current: 5 A (N/O contact)
3.5 A (N/C contact)
Maximum inrush current: 6 A
Inrush current, minimum: 10 mA
Sq. Total current: 50 A2
Interrupting rating (ohmic load) max.: 144 W (N/O contact, 24 V DC, τ = 0 ms)
288 W (N/O contact, 48 V DC, τ = 0 ms)
88 W (N/O contact, 110 V DC, τ = 0 ms)
110 W (N/O contact, 220 V DC, τ = 0 ms)
1500 VA (N/O contact, 230 V AC, τ = 0 ms)
Switching capacity: min. 50 mW
Switching capacity in accordance with IEC 60947-5-1: 3 A (24V (DC13))
3 A (230V (AC15))
Output fuse: 6 A gL/gG (N/O contact)
4 A gL/gG (N/O contact, for low-demand applications)
4 A gL/gG (N/C contact)
Connection dataConnection technology
pluggable: no
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.6 Nm
SignalingOperating voltage display: 1 x yellow LED
DimensionsWidth: 17.5 mm
Height: 75 mm
Depth: 60.5 mm
Material specificationsHousing material: PBT
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 1
Performance level (PL): c
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 1
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 1
Safety data​
Safety Integrity Level (SIL): 1
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -20°C ... 50°C
Ambient temperature (storage/transport): -20°C ... 70°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: N/O contact: 10g, N/C contact: 5g
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Certificate: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: DINEN60947-1
MountingMounting type: DIN rail mounting
Mounting position: vertical or horizontal
Connection method: Screw connection
Technical Specs
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00638.pdf

Approvals_00954.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Certification_00222.pdf

Data_sheet_03975.pdf

Manufacturer_declaration_00598.pdf

Manufacturer_declaration_02371.pdf

Manufacturer_declaration_17020.pdf

Package_slip_02015.pdf

Technical_drawing_41661.pdf