Industrial Automation
PSR-SPF-24UC/URM/4X1/2X2 - Coupling relay


Product properties | Product type: Coupling relay Product family: PSRclassic Application: Safe switch off High demand Low demand Mechanical service life: 10x 106 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/ENÃ61810-3 Times Restart time: < 1 s (Boot time) |
Electrical properties | Maximum power dissipation for nominal condition: 8.71 W (at UBÃ=Ã26.4ÃVÃDC, USÃ=Ã24ÃV, ISÃ=Ã52ÃmA, nÃ=Ã1, IL²Ã=Ã72ÃA², RcontactÃ=Ã0.1Ãïâ¦Ã¢) Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 V Rated surge voltage/insulation: Safe isolation, reinforced insulation 6ÃkV between input circuit (A1/A2) and all output current paths Basic insulation 4ÃkV between all output current paths |
Input data | General Rated control circuit supply voltage US: 24 V AC/DC -20Ã%Ã/Ã+10Ã% Power consumption at US: typ. 1.25 W Rated control supply current IS: typ. 52 mA Input voltage range: 19.2 V AC/DC ... 26.4 V AC/DC Typ. starting time with Us: typ. 10 ms (when controlled via A1) Typical release time: typ. 10 ms (when controlled via A1) Recovery time: < 500 ms Maximum switching frequency: 0.5 Hz Operating voltage display: 1 x green LED |
Output data | Contact switching type: 4 enabling current paths 2 confirmation current paths Contact material: AgSnO2 Maximum switching voltage: 230 V AC/DC (Observe the load curve) Minimum switching voltage: 5 V AC/DC Limiting continuous current: 6 A (N/O contact) 6 A (N/C contact) Maximum inrush current: 6 A Inrush current, minimum: 10 mA Sq. Total current: 72 A2 Interrupting rating (ohmic load) max.: 144 W (N/O contact, 24 V DC, Ãâ = 0 ms) 288 W (N/O contact, 48 V DC, Ãâ = 0 ms) 77 W (N/O contact, 110 V DC, Ãâ = 0 ms) 88 W (N/O contact, 220 V DC, Ãâ = 0 ms) Maximum interrupting rating (inductive load): 48 W (N/O contact, 24 V DC, Ãâ = 40 ms) 40 W (N/O contact, 48 V DC, Ãâ = 40 ms) 36 W (N/O contact, 60 V DC, Ãâ = 40 ms) 35 W (N/O contact, 110 V DC, Ãâ = 40 ms) 33 W (N/O contact, 220 V DC, Ãâ = 40 ms) Switching capacity: min. 50 mW Switching capacity in accordance with IEC 60947-5-1: 5 A (24ÃV (DC13)) 5 A (230 V (AC 15)) Output fuse: 10 A gL/gG (N/O contact) 4 A gL/gG (N/O contact, for low-demand applications) 6 A gL/gG (N/C contact) |
Connection data | Connection technology pluggable: no Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm Tightening torque: 0.6 Nm |
Dimensions | Width: 40 mm Height: 114.5 mm Depth: 50.1 mm |
Characteristics | Safety data Stop category: 0 Safety data: ENÃISOÃ13849 Category: 1 Performance level (PL): c Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 1 Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 1 Safety dataââ¬Ã¢¹ Safety Integrity Level (SIL): 1 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ââ°¤ 2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g (In the event of stress caused by shock, contact reactions are possible for up to 2Ãms.) Vibration (operation): 10ÃHzÃ...Ã150ÃHz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 2Ãms.) |
Approvals | CE Certificate: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINÃENÃ50178 |
Mounting | Mounting type: DIN rail mounting Mounting position: vertical or horizontal Connection method: Spring-cage connection |