Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2981486
PHOENIX CONTACTNot available

PSR-SCP- 24DC/SDC4/2X1/B - Safety relays

Safety relay for emergency stop, safety door, and solenoid switches and for light grids, up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, 2 N/O contacts, TBUS interface, automatic or manual activation, plug-in screw connection terminal blocks
Product Code: 2981486
Partner cod.: 2981486
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Safety relays
Product family: PSRclassic
Application: Emergency stop
Safety door
Light grid
Solenoid switch
Mechanical service life: approx. 107 cycles
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Electrical propertiesMaximum power dissipation for nominal condition: 1.68 W
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 V
Rated surge voltage/insulation: 4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV between input circuit and enabling current paths.)
Input dataGeneral
Rated control circuit supply voltage US: 24 VDC
Voltage range with reference to US: 0.85 ... 1.1
Power consumption at US: typ. 1.7 W
Rated control supply current IS: typ. 70 mA
Voltage at input/start and feedback circuit: approx. 24 VDC
Typical response time: 20 ms (manual start)
150 ms (automatic start)
Typical release time: 10 ms
Recovery time: 1 s
Protective circuit: Reverse polarity protection; Suppressor diode ()
Max. permissible overall conductor resistance: 50 Ω (Input and start circuits at US)
Output dataContact switching type: 2 enabling current paths
1 semiconductor signaling output
Contact material: AgSnO2
Maximum switching voltage: 250 V AC/DC (Enabling current paths)
24 V (signal output)
Minimum switching voltage: 15 V AC/DC (Enabling current paths)
Limiting continuous current: 6 A (Enabling current paths)
100 mA (signal output)
Maximum inrush current: 6 A
Inrush current, minimum: 25 mA (Enabling current paths)
Sq. Total current: 72 A2 (ITH2 = I12 + I22)
Interrupting rating (ohmic load) max.: 144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
77 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load): 48 W (24VDC, τ=40ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
Switching capacity: min. 0.4 W (Enabling current paths)
Switching capacity (360/h cycles): 6 A (24VDC)
5 A (230 V (AC15))
Switching capacity (3600/h cycles): 3 A (24V (DC13))
3 A (230 V (AC15))
Output fuse: 10 A gL/gG NEOZED (Enabling current paths)
Miniature circuit breaker C6 (24V/20A power supply unit)
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
DimensionsWidth: 22.5 mm
Height: 99 mm
Depth: 114.5 mm
Material specificationsHousing material: Polyamide
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 4 (Undelayed contacts)
Performance level (PL): e
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 3
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -20°C ... 55°C
Ambient temperature (storage/transport): -40°C ... 70°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60664-1
MountingMounting type: DIN rail mounting
Mounting position: any
Connection method: Screw connection
Technical Specs
ECLASSECLASS-11.0: 27371819
ECLASS-13.0: 27371819
ECLASS-12.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Description
Safety relay for emergency stop, safety door, and magnetic switches, as well as light grid, up to SIL 3 or Cat. 4, PL e according to EN ISO 13849, 2 N/O contacts, TBUS interface, automatic or manual activation, plug-in screw connection terminal blocks
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00187.pdf

Approvals_00188.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Data_sheet_03980.pdf

Manufacturer_declaration_00583.pdf

Manufacturer_declaration_02366.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_17027.pdf

Package_slip_01880.pdf

Technical_drawing_41668.pdf