Industrial Automation
Product properties | Product type: Single solid-state relay Operating mode: 100% operating factor Insulation characteristics Insulation: Basic insulation Insulation characteristics: Standards/regulations Insulation: Basic insulation Overvoltage category: III Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 0.17 W Test voltage (Input/output): 2.5 kV (50Hz, 1min., input/output) Standards/regulations Rated insulation voltage: 250 VAC |
Input data | Nominal input voltage UN: 24 VDC Input voltage range in reference to UN: 0.8 ... 1.2 Input voltage range: 19.2 VDC ... 28.8 VDC Switching threshold "0" signal, voltage: < 8.4 VDC Switching threshold "1" signal voltage: > 18 VDC Typical input current at UN: 7 mA Typical response time: 10 ms Typical turn-off time: 10 ms Protective circuit: Reverse polarity protection; Polarity protection diode Transmission frequency: 10 Hz |
Output data | Contact switching type: 1 N/O contact Design of digital output: electronic Output nominal voltage: 230 VAC Output voltage range: 24 VAC ... 253 VAC Limiting continuous current: 2 A (see derating curve) Maximum inrush current: 30 A (10 ms) Min. load current: 25 mA Leakage current: typ. 1 mA Surge current: 30 A (10 ms) Max. load value: 4 A2s (tp = 10ms, at 25°C) Voltage drop at max. limiting continuous current: ⤠1 V Output circuit: 2-conductor floating, zero voltage switch Protective circuit: Surge protection; RC element |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/60fd1c85eee35444a4ff80d7039bb135/-S204x204-FJPG Width: 12.7 mm Height: 29 mm Depth: 15.7 mm |
Material specifications | Flammability rating according to UL 94: V0 (Housing) |
Environmental and real-life conditions | Ambient conditions Degree of protection: RT III Ambient temperature (operation): -25°C ... 60°C Ambient temperature (storage/transport): -25°C ... 70°C |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | Standards/regulations Standards/regulations: IEC 60664 EN50178 |
Mounting | Assembly instructions: See derating curve Mounting position: any |
ECLASS | ECLASS-11.0: 27371604 ECLASS-12.0: 27371604 ECLASS-13.0: 27371604 |
ETIM | ETIM 9.0: EC001504 |
UNSPSC | UNSPSC 21.0: 39122300 |
Description other products