Industrial Automation
IB IL 24 PSDI 8-PAC - Safety module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2182c65be3908e489150116208cdf69e/-S204x204-FJPG Width: 48.8 mm Height: 119.8 mm Depth: 71.5 mm Note on dimensions: Housing dimensions |
Interfaces | Inline local bus No. of channels: 2 Connection method: Inline data jumper Transmission speed: 500 kbps / 2 Mbps (can be switched) |
System properties | Module ID code (dec.): 163 ID code (hex): A3 Length code (hex): 04 Length code (dec): 04 Process data channel: 8 Byte Input address area: 8 Byte ((Operating mode: SafetyBridge)) Output address area: 8 Byte ((Operating mode: SafetyBridge)) Register length: 8 Byte Required parameter data: 1 Byte ((Operating mode: SafetyBridge)) Required configuration data: 5 Byte ((Operating mode: SafetyBridge)) |
Input data | Digital Input name: Digital inputs Description of the input: IEC 61131-2 type 3 Number of inputs: 4 (for 2-channel assignment) 8 (for 1-channel assignment) Cable length: max. 200 m (200 m from the clock output to the safe input (total based on forward and return path)) Connection method: Spring-cage connection Connection technology: 2-, 3-, 4-conductor Input voltage: 24 VDC (via clock outputs UT1 and UT2 or external supply) Input voltage range: -3 VDC ... 30 VDC Input voltage range "0" signal: -3 VDC ... 5 VDC Input voltage range "1" signal: 11 VDC ... 30 VDC Typical input current per channel: 4.2 mA (at 24V) Typical response time: See technical data |
Product properties | Type: modular Product type: I/O component Product family: Inline Application: Functional safety |
Electrical properties | Maximum power dissipation for nominal condition: 24.12 W Transmission medium: Copper Potentials: Communications power (U Supply voltage: 7.5 VDC (see safety data) Current draw: max. 180 mA Potentials: Main circuit supply (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 825 mA (see safety data) typ. 25 mA (plus current consumption of the inputs when supplied via the clock outputs, plus current consumption of the connected initiators when via through the clock outputs) Supply: Module electronics Supply voltage: 24 VDC (via voltage jumper) Supply voltage range: 19.2 VDC ... 30 VDC Electrical isolation/isolation of the voltage ranges Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics): 500 VAC, 50 Hz, 1 min. Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics): 500 VAC, 50 Hz, 1 min. Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O): 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector pluggable: yes Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C Degree of protection: IP20 Air pressure (operation): 80 kPa ... 108 kPa (up to 2000m above sea level) Air pressure (storage/transport): 66 kPa ... 108 kPa (up to 3500m above sea level) Ambient temperature (storage/transport): -25°C ... 70°C Permissible humidity (operation): 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) Permissible humidity (storage/transport): 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products