Industrial Automation
STS 6 - Feed-through terminal block


Product properties | Product type: Feed-through terminal block Number of connections: 2 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 1.31 W |
Connection data | Number of connections per level: 2 Nominal cross section: 6 mm² 1 level Stripping length: 12 mm Internal cylindrical gage: A5 Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.2 mm² ... 10 mm² Cross section AWG: 24 ... 8 (converted acc. to IEC) Conductor cross section flexible: 0.2 mm² ... 6 mm² Conductor cross section, flexible [AWG]: 24 ... 10 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.25 mm² ... 6 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.25 mm² ... 6 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 1.5 mm² Nominal current: 41 A Maximum load current: 57 A (with 10 mm² conductor cross section) Nominal voltage: 800 V Nominal cross section: 6 mm² |
Dimensions | Width: 8.2 mm End cover width: 2.2 mm Height: 58 mm Depth on NSÃ35/7,5: 50 mm Depth on NSÃ35/15: 57.5 mm |
Material specifications | Color: gray Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Calorimetric heat release NFPA 130 (ASTM E 1354): 27,5 MJ/kg Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Electrical tests | Surge voltage test Test voltage setpoint: 9.8 kV Result: Test passed Temperature-rise test Requirement temperature-rise test: Increase in temperature ââ°¤Ã45ÃK Result: Test passed Short-time withstand current 6 mm²: 0.72 kA Short-time withstand current 10 mm²: 1.2 kA Power-frequency withstand voltage Test voltage setpoint: 2.2 kV Result: Test passed |
Mechanical properties | Mechanical data Open side panel: Yes |
Mechanical tests | Mechanical strength Result: Test passed Attachment on the carrier DIN rail/fixing support: NSÃ35 Test force setpoint: 5 N Result: Test passed Test for conductor damage and slackening Rotation speed: 10Ãrpm Revolutions: 135 Conductor cross section/weight: 0.2 mm² / 0.3 kg 6 mm² / 1.4 kg 10 mm² / 2 kg Result: Test passed |
Environmental and real-life conditions | Aging Temperature cycles: 192 Result: Test passed Needle-flame test Time of exposure: 30 s Result: Test passed Oscillation/broadband noise Specification: DINÃENÃ50155 (VDEÃ0115-200):2008-03 Spectrum: Service life test categoryÃ2, bogie-mounted Frequency: f1 = 5 Hz to f2 = 250 Hz ASD level: 6.12 (m/s²)²/Hz Acceleration: 3.12g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: DINÃENÃ50155 (VDEÃ0115-200):2008-03 Pulse shape: Half-sine Acceleration: 30g Shock duration: 18Ãms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) Result: Test passed Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24Ãh, -60ðC to +70ðC) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 |
Mounting | Mounting type: NS 35/7,5 NSÃ35/15 |
Description other products