Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

ROCKWELL AUTOMATION 104-K12KJ02
ROCKWELL AUTOMATION 104-K12KJ02
ROCKWELL AUTOMATION 104-K12KJ02
ROCKWELL AUTOMATIONNot available

Miniature Reversing Contactor, Screw Type Terminals, 12 A, IEC, 24V 50/60Hz, 3 N.O. Poles, 1 N.C.

104-K Mini Reversing Contactors, Screw Type Terminals, 12A, System Control Voltage: 24V 50/60Hz, 3 N.O. Main Contacts, 1 N.C. Auxiliary Contact
Product Code: 104-K12KJ02
Partner cod.: 104-K12KJ02
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Voltage type for actuatingAC
Rated control supply voltage at AC 50 Hz24 V
Rated control supply voltage at AC 60 Hz24 V
Rated control supply voltage at DC0 V
Rated impulse withstand voltage (Uimp)6 kV
Current (Ie), max12 A
Power dissipation by all circuits at Ie AC-3/400V0.9 W
Main current circuit resistance2.2 mOhm
Current rating5 A
Rated isolation voltage (Ui)690V per IEC
Rated voltage (Ue)690V @ AC, 50/60 Hz
Auxiliary contact configuration1 NC
Rated filament current9 A @ 230/240V, AC-5b
Switching of motor load for home appliances11 A @ 400V, AC-7b (50 Hz)
Rated current (enclosed)9.6 A @ 230V, 3-phase per UL/CSA
Rated power (enclosed)7.5 Hp @ 575V, 3-phase per UL/CSA
General purpose current (enclosed)18 A per UL/CSA
Switching of low inductive loads in home appliances20 A @ 400V, AC-7a per IEC 61095 (50 Hz)
Coil operating limits, pick-up(0.85...1.1) x Us @ 50 Hz, 60 Hz, 50/60 Hz
Coil operating limits, dropout(0.2...0.75) x Us @ 50 Hz, 60 Hz, 50/60 Hz
Coil operating time15...40 ms, closing delay @ AC
Short time withstand (Icw)96 A for 10 s, 60 °C
Coil consumption, hold-in5VA/1.8 W @ 50 Hz, 60 Hz, 50/60 Hz
Switching frequency, max250 ops/h, AC-4 (approximately 200000 operations)
Coil consumption, pick-up35VA @ 50 Hz, 60 Hz, 50/60 Hz
Total power dissipationDC control: 3.5 W @ 400V, AC-3, Ie
Switching of lampsGas discharge lamps, open: 18 A @ 40 °C, AC-5a
Switching of hermetically sealed cooling compressor motors18 A @ 400V, AC-8a (manual reset of overload release (50 Hz))
Coil insulation classClass F per IEC 60085, Class 105 insulation system per UL 508
Rating for switching AC motors3-poles: 5.5 kW @ 690V (AC-2, AC-3, AC-4), 3-phase (50 Hz)
UL class K5 and RK5 fuses rating40 A @ 600V, 5 kA available fault current per UL 508 and CSA 22.2 No. 14
UL class CC and CSA HRCI-MISC fuses rating30 A @ 600V, 50 kA available fault current per UL 508 and CSA 22.2 No. 14
Coil voltage24V 50/60 Hz
Rated operational current (Ie)9.2 A @ 500V, AC-4, 50 Hz, 3-phase, ambient temperature 60 °C
Rated operational power (Pe)8.3 kW @ 240V, AC-1 (50 Hz), ambient temperature 40 °C
DIN fuses (gG, gL) current ratingType 2 (per IEC 60947-4-1): 20 A @ 400 V, 50 kA available fault current
UL class J and CSA HRCI-J fuses rating30 A @ 600V, 50 kA available fault current per UL 508 and CSA 22.2 No. 14
Switching of power transformersApparent power: 5 kVA @ 690V, AC-6a, 50 Hz (n = 30)
Switching of DC loads3-poles in series: 9 A @ 48/60V (Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C)
Contacts3 power poles with internal NC auxiliary contact
FunctionReversing contactor
Conductor cross section per UL/CSA18 AWG
Terminal typeScrew terminals
Rated coil frequencyAC 50/60 Hz, DC
Function or layoutNothing specified
Vibration resistanceIEC 60068-2
Shock resistanceIEC 60068-2
Recommended torque10.6 lb.in
Conductor cross section0.75...2.5 mm², 2 conductors @ main contact
LifespanMechanical DC control: 15000000 ops
Type of electrical connection of main circuitScrew connection
Auxiliary contactsIP2X
Altitude of installation site, max2000 m (NN), per IEC 60947-4
Ambient temperatureStorage: -55...80 (-67...176)
Degree of protection (IP)IP2X
Optional overload relaysBimetallic
Optional accessoriesFront-mount auxiliary contacts, surge suppressors, electronic timers, mechanical interlocks
FeaturesMini-contactors, Uniform panel mounting dimensions, Panel mounting or mounting on 35 mm DIN Rail, Made of environmentally friendly materials
Climatic withstandIEC 60068-2-30