ROCKWELL AUTOMATION 140G-H0I3-D10
ROCKWELL AUTOMATION 140G-H0I3-D10
ROCKWELL AUTOMATIONNot available

Molded Case Ckt-Bkr, 125A H Frame, 100 kA at 480V, ElecLSIG -Lg&ShTm, HghInst, GFlt, 3 Poles, 100A, 80 Percent MCCB, No Bus Bar Mounting, NONE, None, NONE, None

140G - Molded Case Circuit Breaker, H frame, 100 kA Interrupt Rating, LSIG (electronic), 3 Poles, Rated Current 100 A
Product Code: 140G-H0I3-D10
Partner cod.: 140G-H0I3-D10
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
Number of poles3
With integrated under voltage releaseNo
Integrated earth fault protectionYes
Complete device with protection unitYes
Rated permanent current Iu100 A
Type of control elementToggle
Rated impulse withstand voltage (Uimp)8 kV
Frame size125 A
Voltage for reverse-fed circuit breaker, max480V AC per UL/CSA
Watt lossElectronic type: 12.6 W
Protection typeâۉ€Electronic I (instantaneous trip units)I3 = 1...10 x In (100...1000 A)
Insulation voltage (Ui)Rated 1000V per IEC
Electrical life cycle8000 @ 415V AC
Protection typeâۉ€Electronic L (long time trip units)I1 = 0.4...1 x In (40...100 A), t1 = 3, 12, 36, 60 sec
Protection typeâۉ€Electronic G (ground fault trip units)I4 = 0.2...1 x In (20...100 A), t2 = 0.1, 0.2, 0.4, 0.8 sec
Protection typeâۉ€Electronic S (short time trip units)I2 = 1...10 x In (100...1000 A), t2 = 0.05, 0.1, 0.2, 0.4 sec
Operating current (In), max93 A @ 50 °C (122 ËÅ¡F) per UL
Interrupting rating35 kA @ 600V AC, 50/60 Hz per NEMA, UL, CSA
Rated ultimate short-circuit breaking capacity (Icu)IEC 60947-2: 85 kA @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Rated service short-circuit breaking capacity (Ics)IEC 60947-2: 100% lcu @ 500V DC, 3-poles in series, thermal-magnetic trip unit only
Protection typeElectronic LSIG-long and short time, high Instantaneous, ground fault
Motor drive integratedNo
With switched-off indicatorNo
Motor drive optionalYes
Position of connection for main current circuitFront side
Type of electrical connection of main circuitScrew connection
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Degree of protection (IP)IP40
Weight2.65 lb
Mechanical life operations25000 /h
Vibration2...13.2 Hz ±1 mm, 13.2...100 Hz ±0.7 G
ShockPeak acceleration: 150 m/s^2 peak, pulse duration 11 ms
Factory optionNone
Height130 mm
Device constructionBuilt-in device fixed built-in technique
Width90 mm
Depth82.5 mm
Storage temperature-40 °F
Wire temperature ratingCu 75 °C
Operational voltage (Ue)90% of voltage rating @ 3000 meter (9840 ft) altitude
Rated uninterrupted current (Iu)98% of current rating @ 3000 meter (9840 ft) altitude
Ambient temperature without derating104 °F